Date |
Text |
2007-04-08 10:10:06 | ** UNSAT ** |
| |
| 1) NOTE: PLEASE SEE THAT NOT ALL SHEETS ARE SIGNED, |
| DATED AND SEALED BY THE ENGINEER OF RECORD. |
| FS 471.025, FAC 61G15-23.002 |
| |
| 2) NOTE: PLEASE SEE THE PLANS WERE ISSUED FOR PERMIT |
| WITH *NOTES REDLINED* AND ATTACHED TO PLANS. PLEASE SEE |
| TO DATE THAT NO DOCUMENTATION AHS BEEN VERIFIED FOR |
| COMPLIANCE TO MEET THE EXCEPTIONS OF THE NEC FOR |
| DISCONNECTING MEANS ETC AS PREVIOUSLY GONE OVER FOR THE |
| DETACHED BUILDING. |
| PLEASE SEE 225.31-225.398 |
| PLEASE SEE THE NOTES BELOW ARE TAKEN FROM THE ISSUED |
| PLANS AND PERMITS FOR SCOPE OF WORK. |
| PLEASE PROVIDE COMPLETED DOCUMENTATION FOR EXCEPTION OF |
| *SAFE PROCEDURES*, *QUALIFIED PERSONNEL* ON-SITE 24/7 |
| ETC, PAPERWORK AND DOCUMENTATION MUST BE ORIGINAL, |
| SIGNED, AND NOTARIZED. |
| IF THIS IS NOT MET THEN PLANS AS ORIGINALLY NOTED WILL |
| NEED TO BE REVISED TO MEET NEC CODE COMPLIANCE. |
| |
| 3) NOTE: PLEASE ALSO SEE THAT AS TO DATE OUR RECORDS DO |
| NOT INDICATE ANY LOW VOLTAGE PERMIT WHICH HAS BEEN |
| APPLIED FOR OR ISSUED FOR THIS PROJECT. |
| PLEASE SEE NOTES REDLINED ON PLANS WHICH MENTION THIS |
| IS TO BE UNDER A SEPARATE PERMIT. |
| |
| |
| |
| ************** NOTES REDLINED******* |
| |
| *** LOW VOLTAGE WIRING UNDER A SEPARATE PERMIT. |
| |
| |
| **** 1) NOTE: PLEASE KNOW UPON READING RESPONSE FROM |
| DESIGN TEAM, THIS OFFICE IS WELL AWARE THAT THE |
| STRUCTURE MAY BE FED WITH OTHER SYSTEMS AS LISTED IN |
| 225.30.PLEASE SEE PREVIOUS NOTES WHICH WAS WITH |
| RESPECT TO DISCONNECTING MEANS REQUIRED ETC. PLEASE SEE |
| THE FOLLOWING EXCEPTION WHICH IS TAKEN DIRECTLY FROM |
| THE NEC WILL BE REQUIRED TO BE VERIFIED ON SITE.THIS |
| WAS RED-LINED ON E-5. |
| "EXCEPTION NO. 1: FOR INSTALLATIONS UNDER SINGLE |
| MANAGEMENT, WHERE DOCUMENTED SAFE SWITCHING PROCEDURES |
| ARE ESTABLISHED AND MAINTAINED FOR DISCONNECTION, AND |
| WHERE THE INSTALLATION IS MONITORED BY "QUALIFIED |
| INDIVIDUALS", THE DISCONNECTING MEANS SHALL BE |
| PERMITTED TO BE LOCATED ELSEWHERE ON THE PREMISES " |
| |
| ** PLEASE SEE NEC ART: 100 FOR*QUALIFIED PERSON*. ONE |
| WHO HAS SKILLS AND KNOWLEDGE RELATED TO THE |
| CONSTRUCTION AND OPERATION OF THE ELECTRICAL EQUIPMENT |
| AND INSTALLATIONS AND HAS RECEIVED SAFETY TRAINING ON |
| THE HAZARDS INVOLVED. |
| EXCERPT FROM HANDBOOK: |
| "NEW IN THE 2002 EDITION, THE DEFINITION OF THE TERM |
| QUALIFIED PERSON NOW INCLUDES SAFETY TRAINING. NO |
| LONGER IS IT ADEQUATE FOR AN ELECTRICAL WORKER TO BE |
| *FAMILIAR WITH THE HAZARDS INVOLVED*; THE ELECTRICAL |
| WORKER OF TODAY MUST ALSO HAVE SAFETY TRAINING ON THE |
| HAZARDS INVOLVED. " |
| |
| ** PLEASE KNOW THESE QUALIFIED PERSON(S) SHALL BE |
| VERIFIED EMPLOYED BY AND ON SITE 24/7, IF THIS CAN NOT |
| BE VERIFIED, ELECTRICAL INSTALLATION AS SHOWN MAY NEED |
| TO BE ADJUSTED TO MEET CODE. |
| THIS PLANS EXAMINER CAN NOT VERIFY AND WILL BE THE |
| RESPONSIBILITY OF THE ENGINEERING / DESIGN TEAM, |
| LICENSED ELECTRICAL CONTRACTOR AND ELECTRICAL |
| INSPECTOR. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |