2006-12-13 15:13:18PROVISOR.
  
 NEC 2002: ARTICLE 645.2 #5THE WALL AND FLOORS OF THE
 INFORMATION TECHNOLOGY EQUIPMENT ROOM SHALL HAVE A FIRE
 RATING NOT LESS THAN 1 HOUR. SEE NFPA 75:5.1.3 FOR MORE
 INFORMATION.THE EXISTING WALLS SHALL MEETS THIS
 REQUIREMENT AS WELL.