2006-07-20 00:00:00 | DENIED:2004 FLORIDA BUILDING CODE |
| |
| 1.PLAN SHEET S2 DETAIL 1 & 3, |
| INDICATES A NEW CAP PLATE & I-BEAM TO BE |
| WELDED ONTO THE EXISTING POST. |
| DEMENSION OF 6" BETWEEN THE ROOF SURFACE |
| AND BOTTOM OF THE OF THE I-BEAM IS 6" |
| WITH THE CONDENSING UNITS LEGS ARE 2' |
| LONG.PER 2004 FBC 1509.7 WHERE ROOFING |
| MATERIALS EXTEND BENEATH THE UNIT ON |
| REAISED EQUIPMENT SUPPORTS, THE MINIMUM |
| CLEARANCE SHALL BE IN ACCORDANCE WITH |
| TABLE 1509.7 FROM THE ROOF SURFACE WO |
| THE BOTTOM OF THE SUPPORT RAIL.THE 6" |
| DOES NOT MEET THIS REQUIREMENT. |
| |
| 2.PLEASE CLARIFY DETAIL ON PLAN SHEET |
| M-3.REFRIGERANT LINES THROUGH THE |
| BUILDING TO THE ROOF SHALL COMPLY WITH |
| 2004 FBC 1514.2.5 THROUGH 1514.2.5.2 |
| |
| 3.PLEASE NOTE, REFRIGERANT LINS SHALL |
| COMPLY WITH ASHRAE 62-2001 |
| |
| 4.PLAN SHEET A-2 INDICATES A DETAIL |
| FOR PATE CURB FOR MULTPLE PIPES |
| PENETRATIONS.ARCHITECTURAL PLANS DO |
| NOT SHOW DETAIL OF THE GALVANIZED TROUGH |
| AS INDICATED ON PLAN SHEET M-3. |
| |
| 5.PLEASE CLARIFY THE REFRIGERANT |
| PIPING DETAIL THRU ROOF SHOWN ON PLAN |
| SHEET M-4.THIS INDICATES INSULATED |
| PIPING THROUGH CONCRETE ROOF SLAB, SHOW |
| COMPLIANCE WITH 2004 FMC 1107.2.1. |
| DETAIL ALSO INDICATES COUNTER FLASHING |
| TO BE SAME MATERIAL AS THE PIPE AND IS |
| TO BE SOLDERED TO REFRIGERANT LINE.IS |
| THIS CORRECT? |
| |