Plan Review Notes
Plan Review Notes For Permit 06061475
Permit Number 06061475
Review Stop M
Sequence Number 2
Notes
Date Text
2006-07-20 00:00:00DENIED:2004 FLORIDA BUILDING CODE
  
 1.PLAN SHEET S2 DETAIL 1 & 3,
 INDICATES A NEW CAP PLATE & I-BEAM TO BE
 WELDED ONTO THE EXISTING POST.
 DEMENSION OF 6" BETWEEN THE ROOF SURFACE
 AND BOTTOM OF THE OF THE I-BEAM IS 6"
 WITH THE CONDENSING UNITS LEGS ARE 2'
 LONG.PER 2004 FBC 1509.7 WHERE ROOFING
 MATERIALS EXTEND BENEATH THE UNIT ON
 REAISED EQUIPMENT SUPPORTS, THE MINIMUM
 CLEARANCE SHALL BE IN ACCORDANCE WITH
 TABLE 1509.7 FROM THE ROOF SURFACE WO
 THE BOTTOM OF THE SUPPORT RAIL.THE 6"
 DOES NOT MEET THIS REQUIREMENT.
  
 2.PLEASE CLARIFY DETAIL ON PLAN SHEET
 M-3.REFRIGERANT LINES THROUGH THE
 BUILDING TO THE ROOF SHALL COMPLY WITH
 2004 FBC 1514.2.5 THROUGH 1514.2.5.2
  
 3.PLEASE NOTE, REFRIGERANT LINS SHALL
 COMPLY WITH ASHRAE 62-2001
  
 4.PLAN SHEET A-2 INDICATES A DETAIL
 FOR PATE CURB FOR MULTPLE PIPES
 PENETRATIONS.ARCHITECTURAL PLANS DO
 NOT SHOW DETAIL OF THE GALVANIZED TROUGH
 AS INDICATED ON PLAN SHEET M-3.
  
 5.PLEASE CLARIFY THE REFRIGERANT
 PIPING DETAIL THRU ROOF SHOWN ON PLAN
 SHEET M-4.THIS INDICATES INSULATED
 PIPING THROUGH CONCRETE ROOF SLAB, SHOW
 COMPLIANCE WITH 2004 FMC 1107.2.1.
 DETAIL ALSO INDICATES COUNTER FLASHING
 TO BE SAME MATERIAL AS THE PIPE AND IS
 TO BE SOLDERED TO REFRIGERANT LINE.IS
 THIS CORRECT?
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  