2006-06-29 00:00:00 | *** UNSAT *** |
| |
| 1) NOTE: PLEASE SEE ADDRESSING SHALL |
| CORRELATE, AS THE APPLICATION SHOWS 901 |
| S FLAGLER, THE PCN USED IS FOR 900 S |
| OLIVE, AND PLANS SHOWS 1101 S OLIVE. |
| PLEASE KNOW, ALL THESE SHALL CORRELATE |
| AND ONCE THE "ADDRESS" IS CORRECTED, |
| PLEASE MAKE SURE ALL TITLE BLOCKS ON ALL |
| SHEETS ARE CORRECTED. |
| FAC 61G1-16.004 |
| |
| 2) NOTE: PLEASE SEE COVER SHEETS STATES |
| DESIGN PER 2001 FBC, WHERE WE ARE |
| CURRENTLY UNDER THE 2004 FBC. |
| |
| 3) NOTE: PLEASE SEE PLANS SHALL INCLUDE |
| ALL THE CURRENT CODES ADOPTED AND IN |
| AFFECT IN THE STATE OF FLORIDA. |
| PLEASE SEE THE FOLLOWING CODES SHALL BE |
| STATED ON PLANS AT A MINIMUM. |
| NFPA-70 2002, NFPA-101 2003, NFPA-72 |
| 2002, NFPA-75 2003. |
| |
| 4) NOTE: PLEASE SEE VALUE FOR COMPLETE |
| SCOPE OF WORK SHALL BE ADJUSTED TO |
| INCLUDE ALL LABOR AND MATERIALS. |
| PLEASE KNOW, EVEN IF ANY EQUIPMENT IS |
| SUPPLIED BY THE OWNER. |
| VALUE AT THIS TIME IS LOW. |
| FBC ADMIN SECT 108.3 |
| |
| 5) NOTE: PLEASE SUBMIT MANUFACTURES |
| SPECS/CUT SHEETSFOR ALL NEW UPS |
| EQUIPMENT. |
| 110.3, 106.1.2 |
| |
| 6) NOTE: PLEASE SUBMIT MANUFACTURES |
| SPECS/CUT SHEETS FOR THE NEW ATS BEING |
| PROPOSED. |
| 110.3, FBC106.1.2 |
| |
| 7) NOTE: PLEASE SEE RISER MENTIONS TAPS |
| PER "220.21"? THIS SHOULD BE PER |
| "240.21" |
| PLEASE ALSO KNOW, NOTE MENTIONS NOT TO |
| BE LOCATED MORE THAN 10FT AWAY, HOWEVER |
| PLEASE KNOW AND NOTE ON PLANS, THAT ITS |
| THE CONDUCTOR LENGTH NOT THE DISTANCE. |
| PLEASE ADJUST NOTE. |
| 240.21, 215.5 |
| |
| 8) NOTE: PLEASE CLARIFY PLANS, RISER AS |
| PLANS SEEM TO BE SHOWING THE FEEDERS |
| COMING FROM A SEPARATE, DETACHED |
| BUILDING?? |
| IF THIS IS THE CASE PLEASE SEE |
| 225.31-225.39. |
| PLEASE ADJUST, AND PLEASE VERIFY THE |
| EXISTING AS THIS DOES NOT SEEM TO MEET |
| 225.31-225.39 |
| PLEASE ALSO SEE 250.32 FOR GROUNDING |
| ELECTRODE SYSTEM. |
| |
| 9) NOTE: PLEASE PROVIDE VD CALCULATIONS |
| FOR THE NEW FEEDERS FROM THE EXISTING |
| MAIN ELECTRICAL RM. |
| FBC 2004 13-413.1ABC.1 |
| |
| 10) NOTE: PLEASE PROVIDE A GROUNDING |
| RISER FOR ALL EQUIPMENT,UPS AND |
| ATTACHMENT LOCATION(S). 250.30,250.20, |
| 645.15 |
| |
| ** IMPORTANT** |
| |
| PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS FROM SETS AND ONLY |
| INSERT NEW REVISED SHEETS INTO COMPLETE |
| SETS FOR REVIEW AND STAMPING. |
| PLEASE SUBMIT ONE COPY OF THE OLD/VOIDED |
| SHEETS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |