Date |
Text |
2006-07-18 00:00:00 | 1) ALL PLANS SUBMITTED AFTER OCTOBER, |
| 1,2004 SHALL BE DESIGNED TO THE 2004 |
| FLORIDA BUILDING CODE. |
| |
| 2) 106.1.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| CONSTRUCTION DOCUMENTS SHALL BE |
| DIMENSIONED AND DRAWN UPON SUITABLE |
| MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE |
| PERMITTED TO BE SUBMITTED WHEN APPROVED |
| BY THE BUILDING OFFICIAL. CONSTRUCTION |
| DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN |
| DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THIS CODE AND RELEVANT |
| LAWS, ORDINANCES, RULES AND REGULATIONS, |
| AS DETERMINED BY THE BUILDING OFFICIAL |
| (SEE ALSO SECTION 106.3.5 ). |
| |
| 3) 1509.7 MECHANICAL UNITS. |
| ROOF MOUNTED MECHANICAL UNITS SHALL BE |
| MOUNTED ON CURBS RAISED A MINIMUM OF 8 |
| INCHES (203 MM) ABOVE THE ROOF SURFACE, |
| OR WHERE ROOFING MATERIALS EXTEND |
| BENEATH THE UNIT, ON RAISED EQUIPMENT |
| SUPPORTS PROVIDING A MINIMUM CLEARANCE |
| HEIGHT IN ACCORDANCE WITH ("TABLE |
| 1509.7".) |
| |
| 4) THE ROOF PIPING SUPPORT DETAIL ON |
| SHEE M-3 DOES NOT CORRESPOND WITH THE |
| DETAIL ON SHEET A-2. ALSO ON SHEET M-3, |
| WHERE IS THE GALVANIZED TROUGH DETAIL? |
| NOTE: THE DETAIL SHOWN FOR THE ROOF |
| PIPING PENETRATIONS HAS THE POTENTIAL |
| FOR WATER INTRUSION IN THE FUTURE. |
| |
| 5) INDICATE THE SLOPE OF THE ROOF |
| STRUCTURE WHERE THE MECHINICAL SUPPORTS |
| WILL BE INSTALLED. IF THE ROOD IS |
| SLOPED, SHOW THE ELEVATIONS OF THE |
| MECHNICAL SUPPORTS. |
| |
| 6) FL S S 713.13 |
| NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT BEFORE A |
| PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| IF THE WORK DESCRIBED IN THE NOTICE OF |
| COMMENCEMENT IS NOT ACTUALLY COMMENCED |
| WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. |
| |
| |
| MYRON JACOBS |
| BUILDING PLANS EXAMINER |
| TEL:(561) 805-6726 |
| [email protected] |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |