Plan Review Notes
Plan Review Notes For Permit 06061469
Permit Number 06061469
Review Stop B
Sequence Number 2
Notes
Date Text
2006-08-01 00:00:00DENIED
  
 1) THE DESIGN WIND PRESSURES FOR THE
 WIND AND DOOR OPENINGS ON THE PLANS ARE
 INCORRECT. THE SIMPLIFIED PROVISIONS FOR
 DETERMINING THE WINDLOAD PRESSURES IN
 FBC 1609.6 CAN NOT BE USED FOR BUILDINGS
 MORE THAN 60 FEET IN HEIGHT. WINDLOADS
 FOR THIS STRUCTURE MUST BE DETERMINED BY
 ASCE7-02. SUBMIT SIGNED AND SEALED
 WINDLOAD CALCULATIONS FROM A FLORIDA
 LICENSED DESIGN PROFESSIONAL EXPERIENCED
 IN THIS TYPE OF WORK FOR THE WINDOW AND
 DOOR OPENINGS.
  
 2) PRODUCT APPROVAL FOR THE STORM PANELS
 DOES NOT SPECIFY A FASTENER FOR
 ATTACHMENT TO STEEL. THE IMPACT
 PROTECTION DEVICES ARE REQUIRED TO BE
 TESTED AND MUST MEET THE REQUIREMENTS
 LISTED IN FBC 1609.1.4. YOU CAN NOT
 SPECIFY FASTENERS FROM ANOTHER PRODUCT.
 THEREFORE THEY CAN NOT BE INSTALLED AS
 YOU HAVE INDICATED.
  
 3) THE KEY PLAN SPECIFIES 13'-2" PANELS
 AT THE DOORS. THIS EXCEEDS THE MAXIMUM
 SPAN ALLOWED BY PRODUCT APPROVAL. PLEASE
 CLARIFY.
  
 4) PLEASE USE THE INSTALLATION SCHEDULE
 LOCATED AT THE BACK OF THE IMPACT
 PROTECTION STANDARD ATTACHED TO
 COMMENTS.
  
 5) PLEASE PROVIDE A BREAKDOWN AS TO THE
 TIME IT WILL TAKE TO INSTALL AN
 INDIVIDUAL PANEL, THE NUMBER OF PANELS
 AND THE TOTAL TIME FOR COMPLETE
 INSTALLATION OF ALL PANELS PER REQUEST
 OF BUILDING OFFICIAL.
  
 6) EMERGENCY EGRESS FROM THE UNIT MUST
 BE MAINTAINED WHILE SHUTTERS ARE
 INSTALLED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  