2006-06-29 00:00:00DENIED
  
 1) SPECIFY THE BUILDING HEIGHT AND
 NUMBER OF STORIES ON THE PLANS. FBC
 106.1.2
  
 2) SPECIFY THE POSITIVE AND NEGATIVE
 WIND PRESSURES FOR THE EXTERIOR OPENINGS
 ON THE PLANS. FBC 1603.1.4
  
 3) SHUTTER INSTALLATION ON LARGE OR
 MULTISTORY BUILDINGS REQUIRE PRE-STORM
 PREPARATION PLANS APPROVED BY THE
 CONSTRUCTION SERVICES DEPARTMENT. SEE
 #13 OF THE ATTACHED IMPACT PROTECTION
 STANDARD.
  
 4) THE FASTENER INDICATED (HI-LIGHTED)
 ON THE PRODUCT APPROVAL FOR THE STORM
 PANELS IS FOR ATTACHMENT TO WOOD. THE
 PLANS SPECIFY CONCRETE AND STEEL
 CONSTRUCTION.
  
 5) PROVIDE A KEY PLAN AND INSTALLATION
 SCHEDULE. SPECIFY THE FASTENERS,
 FASTENER SPACING, SPANS, VERTICAL OR
 HORIZONAL INSTALLATION, ETC. A SAMPLE
 INSTALLATION SCHEDULE IS ATTACHED TO THE
 IMPACT PROTECTION STANDARD.
  
 6) IF THE DOORS ARE REQUIRED FOR EGRESS
 EXIT THEY CAN NOT BE SHUTTERED.
  
 7) THE FLORIDA COVERSHEET FOR THE ARCH
 ALUMNIUM DOORS IS FOR IMPACT RATED DOORS
 THE STOREFRONT DOOR NOA IS FOR
 NON-IMPACT DOORS. SUBMIT COVERSHEET AND
 EVALUATION REPORTS FOR THE SAME PRODUCT.
  
 8) THE FLORIDA COVERSHEET FOR THE ARCH
 ALUMINUM STOREFRONT PANEL WALLS DOES NOT
 MATCH THE NOA THAT WAS SUBMITTED.
 COVERSHEET IS FOR IMPACT AND NOA IS FOR
 NON-IMPACT.
  
 9) PROVIDE BUCK ATTACHMENT DETAILS.
  
 10)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  