2006-07-13 00:00:00 | ******DENIED****** | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 CHAPTER 1 | | | | THE FOLLOWING INFORMATION IS REQUIRED | | FOR PLUMBING PLAN REVIEW: | | | | 1. FBC-2004 CHAPTER 1,SECTION 106.3.4.2: | | THE PERSON RESPONSIBLE FOR THE DESIGN OF | | THE DRAWING SHALL CLEARLY PRINT AND SIGN | | NAME. PLEASE DO THIS PRIOR TO RESUBMIT- | | TING. | | 2. FBC-2004 PLUMBING, TABLE 702.2: | | PLEASE INDICATE THE PIPING MATERIAL | | BEING USED ON THE EXISTING AND NEW ISO- | | METRIC SANITARY RISER DIAGRAM ON DRAWING | | NUMBER 2. | | 3. PLEASE CORRELATE THE ISOMETRIC SANI- | | TARY RISER DIAGRAMS WHERE THE WASHING | | MACHINE CLEANOUT LOCATION IS INDICATED | | ON DRAWING NUMBER 2, ONE DRAWING IS | | MISSING THIS INFORMATION. | | | | END OF COMMENTS: | | | | REVIEW BY MIKE PERSON | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | UNDER SUPERVISION OF K.STEVENS | | (561) 805-6721 | | | | |
|