Plan Review Notes
Plan Review Notes For Permit 06061420
Permit Number 06061420
Review Stop E
Sequence Number 1
Notes
Date Text
2006-07-06 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE PERSON TAKING RESPONSIBILITY FOR
 THE PLAN/DRAWINGS, SHALL PRINT AND SIGN
 THEIR NAME ON THE SHEETS DRAW PER
 106.3.4.2 FBC. PLEASE DO THIS PRIOR TO RESUBMITTING.
  
 2} THERE MUST BE A DISCONNECT FROM THE
 GENERATOR WHERE THE CONDUCTORS ENTER THE
 BUILDING. IF ALL DISCONNECTS CANNOT BE
 GROUPED PER 230.72, SEE THAT ALL
 ARTICLES FROM 225.31 THROUGH 225.39, ARE
 COMPLIED WITH.
  
 3} PROVIDE MANUFACTURERS SPECIFICATIONS/RECOMMENDATION,
 REGARDING CLEARANCES FROM STRUCTURES, VENTS, ETC.
  
 4} PROVIDE SPECIFICATIONS FOR THE
 TRANSFER SWITCH.
  
 5} PLEASE LOCATE ALL SERVICE EQUIPMENT
 ON THE PLAN, METER ENCLOSURE, GENERATOR,
 TRANSFER SWITCH, DISCONNECTS AND PANELS,
 SO THAT COMPLIANCE WITH ARTICLES 225 AND
 230 CAN BE REVIEWED.
  
 6} THE VALUE ON THE APPLICATION MUST
 INCLUDE THE COST OF LABOR AND MATERIAL
 FOR THE INSTALLATION OF ALL COMPONENTS
 UNDER THE SCOPE OF THIS PERMIT. FBC
 108.3.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561) 805-6718
  
  