Plan Review Notes For Permit 06061420 |
Permit Number |
06061420 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-07-06 00:00:00 | | | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} THE PERSON TAKING RESPONSIBILITY FOR | | THE PLAN/DRAWINGS, SHALL PRINT AND SIGN | | THEIR NAME ON THE SHEETS DRAW PER | | 106.3.4.2 FBC. PLEASE DO THIS PRIOR TO RESUBMITTING. | | | | 2} THERE MUST BE A DISCONNECT FROM THE | | GENERATOR WHERE THE CONDUCTORS ENTER THE | | BUILDING. IF ALL DISCONNECTS CANNOT BE | | GROUPED PER 230.72, SEE THAT ALL | | ARTICLES FROM 225.31 THROUGH 225.39, ARE | | COMPLIED WITH. | | | | 3} PROVIDE MANUFACTURERS SPECIFICATIONS/RECOMMENDATION, | | REGARDING CLEARANCES FROM STRUCTURES, VENTS, ETC. | | | | 4} PROVIDE SPECIFICATIONS FOR THE | | TRANSFER SWITCH. | | | | 5} PLEASE LOCATE ALL SERVICE EQUIPMENT | | ON THE PLAN, METER ENCLOSURE, GENERATOR, | | TRANSFER SWITCH, DISCONNECTS AND PANELS, | | SO THAT COMPLIANCE WITH ARTICLES 225 AND | | 230 CAN BE REVIEWED. | | | | 6} THE VALUE ON THE APPLICATION MUST | | INCLUDE THE COST OF LABOR AND MATERIAL | | FOR THE INSTALLATION OF ALL COMPONENTS | | UNDER THE SCOPE OF THIS PERMIT. FBC | | 108.3. | | | | WILLIAM R. TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561) 805-6718 | | | | |
|