Plan Review Notes
Plan Review Notes For Permit 06061419
Permit Number 06061419
Review Stop E
Sequence Number 2
Notes
Date Text
2007-01-05 17:51:41 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE VALUE ON THE APPLICATION MUST
 INCLUDE THE COST OF LABOR AND MATERIAL
 FOR THE INSTALLATION OF ALL COMPONENTS
 UNDER THE SCOPE OF THIS PERMIT. FBC
 108.3.CHANGE AMOUNT WHEN RESUBMITTING, TELL CLERK.
  
 2}THE PERSON TAKING RESPONSIBILITY FOR
 THE PLAN/DRAWINGS, SHALL PRINT AND SIGN
 THEIR NAME ON THE SHEETS THEY DRAW.
 PLEASE DO THIS PRIOR TO
 RESUBMITTING.106.3.4.2 FBC.
  
 3} PLEASE LOCATE ALL SERVICE EQUIPMENT
 ON A SITE PLAN, METER ENCLOSURE, GENERATOR,
 TRANSFER SWITCH, DISCONNECTS AND PANELS,
 SO THAT COMPLIANCE WITH ARTICLES 225 AND
 230 CAN BE REVIEWED.
  
 4} PROVIDE A PANEL SCHEDULE PER 408.4.
 FOR THE PANEL BEING FED FROM THE
 GENERATOR.
  
 5} PROVIDE MANUFACTURERS SPECIFICATIONS/RECOMMENDATION,
 REGARDING CLEARANCES.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561) 805-6718
  