Plan Review Notes
Plan Review Notes For Permit 06061419
Permit Number 06061419
Review Stop E
Sequence Number 1
Notes
Date Text
2006-07-07 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE VALUE ON THE APPLICATION MUST
 INCLUDE THE COST OF LABOR AND MATERIAL
 FOR THE INSTALLATION OF ALL COMPONENTS
 UNDER THE SCOPE OF THIS PERMIT. FBC
 108.3.
  
 2}THE PERSON TAKING RESPONSIBILITY FOR
 THE PLAN/DRAWINGS, SHALL PRINT AND SIGN
 THEIR NAME ON THE SHEETS THEY DRAW.
 PLEASE DO THIS PRIOR TO
 RESUBMITTING.106.3.4.2 FBC.
  
 3} PLEASE LOCATE ALL SERVICE EQUIPMENT
 ON THE PLAN, METER ENCLOSURE, GENERATOR,
 TRANSFER SWITCH, DISCONNECTS AND PANELS,
 SO THAT COMPLIANCE WITH ARTICLES 225 AND
 230 CAN BE REVIEWED.
  
 4} PROVIDE SPECIFICATIONS FOR THE
 TRANSFER SWITCH.
  
 5} PROVIDE A PANEL SCHEDULE PER 408.4.
 FR THE PANEL BEING FED FROM THE
 GENERATOR.
  
 6} PROVIDE MANUFACTURERS SPECIFICATIONS/RECOMMENDATION,
 REGARDING CLEARANCES.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561) 805-6718
  