2006-07-03 00:00:00 | ******DENIED****** |
| REFERENCE: FBC-2004 FUEL GAS |
| FBC-2004 CHAPTER 1 |
| |
| THE FOLLOWING INFORMATION IS REQUIRED |
| FOR GAS PLAN REVIEW: |
| |
| 1. PER FBC-2004, CHAPTER 1, SECTION 106 |
| CONSTRUCTION DOCUMENTS: ISOMETRIC |
| DRAWINGS IN PENCIL ARE UNACCEPTABLE. |
| PLEASE PRINT NAME ABOVE THE SIGNATURE |
| AND DATE DRAWING |
| 2. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. (NOTE: THIS INCLUDES THE |
| EXISTING1-1/4" LINE INDICATED ON THE |
| DRAWING) |
| 3. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33).(NOTE: THIS INCLUDES THE BTU'S |
| OF THE EXISTING SYSTEM) |
| 4. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| (NOTE: THIS INCLUDES THE EXISTING |
| SYSTEM, LONGEST LENGTH METHOD USED IN |
| SIZING SYSTEM) |
| 5. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| PLEASE INDICATE PRESSURE ON THE DRAWING. |
| 6. PER FBC-2004 FUEL GAS, SEC. 403.4.1: |
| IRON PIPE SHALL NOT BE USED PLEASE |
| CHANGE TO STEEL OR GALVANIZED. |
| |
| **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. PLEASE SEE CORRECTED DRAWING IN |
| RED INK FOR REFERENCE FOR RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |