2006-06-27 00:00:00 | ******* UNSAT ******* | | | | 1) NOTE: PLEASE CLARIFY WHY AND FOR WHAT | | AREA NEW SERVICE IS BEING REQUESTED. | | PLEASE SEE SERVICE LENDS TO A NEW TENANT | | SPACE, HOWEVER NEED TO VERIFY THIS FOR | | TENANT SEPARATIO ETC BEFORE NEW SERVICE | | CAN BE GRANTED. | | PLEASE SEE LOADS ON EACH PANEL S DO | | INDICATE EXCEEDING ANY RATINGS TO | | REQUEST A NEW SERVICE. | | PLEASE PROVIDE A LAYOUT FOR NEW AND | | EXISTING PANELS. | | 230.2 | | 106.1.2, FBC 2004 | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | RATED FOR THE AVAILABLE FAULT CURRENT. | | PER 110.9/215.5 | | | | 3) NOTE: PLEASE CLARIFY THE EQUIPMENT | | GROUNDING FROM NEW MAIN TO PANEL. | | 250.110,250.24B | | | | 4) NOTE: PLEASE BE SURE THE PRINTED NAME | | AND SIGNATURE IS PROVIDED ON ALL | | PLANS/DESIGN. | | | | PLEASE KNOW ADDITIONAL SERVICE MAY NOT | | BE GRANTED UNTIL SUCH TIME PERMITS FOR | | NEW TENANT SPACE ARE ISSUED. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] | | | | | | |
|