Date Text
2006-07-24 00:00:00 
  
  
 2) THE INSTALLATION RREPORT (APPROVED
 ASSEMBLY)IS MISSING FROM FL#985-RI.
 SUBMIT AN APPROVED ASSEMBLY FROM THE
 PACKAGE. SEE PAGES 39-43. THIS ROOF IS
 ALSO MISSING OR NOT IN COMPLIANCE WITH
 THE FOLLOW ITEMS:
  
 _XX__ CONTRACTOR FAILED TO INDICATE
 WHICH SYSTEM TO BE USED.
  
 _XX__ THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE _3__ .
  
 _XX__ THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 _XX__THE SYSTEM PROVIDED INDICATES
 LIMITATION# 9, NO ENHANCED
  
  
 3)GENERAL LIMITATION #9 PROHIBITS
 RATIONAL ANALYSIS OR EXTRAPOLATION TO
 ENHANCE THE UPLIFT PRESSURE AT PERIMETER
 AND CORNER AREAS BY REDUCING THE
 FASTENER SPACING IN THESE AREAS.EITHER
 SELECT AN ALTERNATIVE SYSTEM (OR PRODUCT
 APPROVAL) THAT DOES NOT CITE GENERAL
 LIMITATION #9.ALTERNATIVELY IF THE
 SELECTED SYSTEM DOES CITE GENERAL
 LIMITATION #9, IT MUST HAVE A MAXIMUM
 DESIGN PRESSURE THAT EXCEEDS THE
 PRESSURE IN ROOF ZONE 3 (TYPICALLY -89
 PSF FOR MEAN ROOF HEIGHT OF 30 FEET OR
 LESS).
  
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726