2006-07-24 00:00:00 | |
| |
| |
| 2) THE INSTALLATION RREPORT (APPROVED |
| ASSEMBLY)IS MISSING FROM FL#985-RI. |
| SUBMIT AN APPROVED ASSEMBLY FROM THE |
| PACKAGE. SEE PAGES 39-43. THIS ROOF IS |
| ALSO MISSING OR NOT IN COMPLIANCE WITH |
| THE FOLLOW ITEMS: |
| |
| _XX__ CONTRACTOR FAILED TO INDICATE |
| WHICH SYSTEM TO BE USED. |
| |
| _XX__ THE SYSTEM PROVIDED HAS A LOW |
| PRESSURE FOR ZONE _3__ . |
| |
| _XX__ THE SYSTEM PROVIDED STATES |
| LIMITATION# 7, SHOULD THE FASTENER |
| RESISTANCE BE LESS THAN THAT |
| REQUIRED, AS DETERMINED BY THE |
| BUILDING OFFICIAL, A REVISED |
| FASTENER SPACING, PREPARED , SIGNED |
| AND SEALED BY A FLORIDA REGISTERED |
| PROFESSIONAL ENGINEER, REGISTERED |
| ARCHITECT OR REGISTERED ROOF |
| CONSULTANT MAY BE SUBMITTED. |
| |
| _XX__THE SYSTEM PROVIDED INDICATES |
| LIMITATION# 9, NO ENHANCED |
| |
| |
| 3)GENERAL LIMITATION #9 PROHIBITS |
| RATIONAL ANALYSIS OR EXTRAPOLATION TO |
| ENHANCE THE UPLIFT PRESSURE AT PERIMETER |
| AND CORNER AREAS BY REDUCING THE |
| FASTENER SPACING IN THESE AREAS.EITHER |
| SELECT AN ALTERNATIVE SYSTEM (OR PRODUCT |
| APPROVAL) THAT DOES NOT CITE GENERAL |
| LIMITATION #9.ALTERNATIVELY IF THE |
| SELECTED SYSTEM DOES CITE GENERAL |
| LIMITATION #9, IT MUST HAVE A MAXIMUM |
| DESIGN PRESSURE THAT EXCEEDS THE |
| PRESSURE IN ROOF ZONE 3 (TYPICALLY -89 |
| PSF FOR MEAN ROOF HEIGHT OF 30 FEET OR |
| LESS). |
| |
| |