Plan Review Notes For Permit 06061339 |
Permit Number |
06061339 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-06-29 00:00:00 | ***DENIED*** | | | | 1) LIFE SAFETY SHALL COMPLY WITH NFPA | | 101, 2003 EDITION. | | | | 2) PLEASE INDICATE THE MINIMUM INTERIOR | | FINISH FOR WALLS AND CEILINGS IN TERMS | | OF CLASS A, B, OR C. | | | | 3) SEPARATE SHOP DRAWINGS AND PERMITS | | ARE REQUIRED FOR FIRE SPRINKLER AND FIRE | | ALARM REMODEL. | | | | 4) IF DUCT SMOKE DETECTOR INSTALLATION | | IS PART OF THE SCOPE OF THIS WORK, THEY | | SHALL INITIATE A GENERAL FIRE ALARM IN | | ACCORDANCE WITH LOCAL REQUIREMENTS. SHT | | E0.1, NOTE (17). | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | FIRE PLAN REVIEW (561) 805-6722 |
|