2006-06-28 00:00:00 | ********** NOTES *********** |
| |
| 1) NOTE: PLEASE CLARIFY IF ALL |
| CONTINUOUS LAODS ARE SHOWN AS EXISTING |
| ALREADY FIGURED OR ADJUST AS NEEDED. |
| 215.3,230.42 ETC |
| |
| 2) NOTE: PLEASE SEE PLANS INDICATE |
| ADDRESS AS BEING "2501" S. AUSTRALIAN?? |
| WHERE AS THE APPLICATION IS FOR "250". |
| THIS BUILDING LAYOUT SEEMS TO BE FOR |
| "250" AND PERHAPS THIS IS ONLY A |
| MISPRINT? |
| |
| 3) NOTE: PLEASE SEE PLANS SHALL BE |
| SPECIFIC IN DESIGNS FOR THE CODES |
| CURRENTLY INEFFECT. |
| PLEASE ADJUST THE FOLLOWING. |
| NFPA-70 2002, NFPA-101 2003, NFPA-72 |
| 2002. |
| |
| ** PLEASE BE SURE TO SEE ANY POSSIBLE |
| COMMENTS FROM OTHER TRADES WHICH MAY |
| AFFECT ELECTRICAL PLANS OR DESIGN. |
| |
| ** IMPORTANT, PLEASE BE SURE TO REMOVE |
| ANY OLD/VOIDED SHEETS AND ONLY INSERT |
| NEW SHEETS INTO COMPLETE SETS FOR REVIEW |
| AND STAMPING. |
| |
| **PLEASE KNOW, FOR SHEETS WHICH MAY NOT |
| HAVE ANY CODE CORRECTIONS TO BE MADE, |
| THE ADDRESS (IF 250) CAN BE CORRECTED BY |
| THE REMOVAL OF THE "1" FROM ADDRESS IN |
| THE TITLE BLOCKS OF ALL SHEETS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |