2006-06-28 00:00:00 | **** UNSAT **** |
| |
| 1) NOTE: PLEASE PROVIDE LOAD ON EXISTING |
| SERVICE W/ NEW LOAD ADDED. PLEASE SEE |
| THAT ALL CONTINOUS LOADS BE SHOWN AT |
| 125%, SHOWN FOR LT AND PUMP, HOWEVER |
| THISIS ALSO REQUIRED FOR HEAT PUMP. |
| 215.3,230.42,430.32,680.9,220.31, 215.5 |
| |
| 2) NOTE: PLEASE SEE NEW 1-1/2 HP PUMP IS |
| SHOWN WITH THREE #8'S ON PLANS AND ON |
| "PANEL SCHEDULE" PROVIDED BY THE |
| ELECTRICAN. PLEASE SEE THE MAX OPC FOR |
| 1/2 HP PUMP SHALL BE SIZED FROM NEC |
| 430.31,32,430.148 |
| PLEASE ALSO SEE 3-#8'S WILL NOT FIT INTO |
| THIS PUMP, OR RATED FOR CONNECTION TO |
| 30A OR 20A BRKR. |
| PLEASE REVISE AND ADJUST CONDUCTOR SIZES |
| ON PLANS AND SHEET ATTACHED TO PLANS. |
| |
| 3) NOTE: PLEASE SEE MISSING EQUIPMENT |
| GROUNDING CONDUCTOR FROM EXISTING |
| SERVICE TO NEW SUB/POOL PANEL. |
| PLEASE SEE 3-#6'S AND 1-#10 IS BEING |
| SHOWN IN A 3/4 INCH CONDUIT, YET THIS |
| CONDUIT IS OVER FILLED BASED ON TABLES |
| FOR CONDUIT FILL IN CHAPTER 9 |
| 250.110,250.122,680.6, 680.25B |
| |
| *** IMPORTANT** |
| 4) NOTE: PLEASE SEE ZONING NOTES, AND |
| PLEASE SEE THAT IT IS KNOWN BY THIS |
| OFFICE THAT THE EXISTING ELECTRICAL |
| METER IS BEING MOVED, HOWEVER THE |
| EXISTING ELECTRICAL SERVICE PANEL IS |
| REMAINING WHERE IT IS AND DOES NOT MEET |
| MIN CLEARENCE REQUIREMENTS PER NEC. 680. |
| PLEASE KNOW, THE EXISTING ELECTRICAL |
| PANEL MUST BE MOVED. |
| |
| ** PLEASE KNOW, EACH PLAN, PANEL |
| SCHEDULE ETC SHALL BE SPECIFIC IN DESIGN |
| TO EACH DWELLING/LOCATION AND POOL BEING |
| DESIGNED. |
| 106.1.1,1.6.1.2 |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |