2006-06-28 00:00:00**** UNSAT ****
  
 1) NOTE: PLEASE PROVIDE LOAD ON EXISTING
 SERVICE W/ NEW LOAD ADDED. PLEASE SEE
 THAT ALL CONTINOUS LOADS BE SHOWN AT
 125%, SHOWN FOR LT AND PUMP, HOWEVER
 THISIS ALSO REQUIRED FOR HEAT PUMP.
 215.3,230.42,430.32,680.9,220.31, 215.5
  
 2) NOTE: PLEASE SEE NEW 1-1/2 HP PUMP IS
 SHOWN WITH THREE #8'S ON PLANS AND ON
 "PANEL SCHEDULE" PROVIDED BY THE
 ELECTRICAN. PLEASE SEE THE MAX OPC FOR
 1/2 HP PUMP SHALL BE SIZED FROM NEC
 430.31,32,430.148
 PLEASE ALSO SEE 3-#8'S WILL NOT FIT INTO
 THIS PUMP, OR RATED FOR CONNECTION TO
 30A OR 20A BRKR.
 PLEASE REVISE AND ADJUST CONDUCTOR SIZES
 ON PLANS AND SHEET ATTACHED TO PLANS.
  
 3) NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM EXISTING
 SERVICE TO NEW SUB/POOL PANEL.
 PLEASE SEE 3-#6'S AND 1-#10 IS BEING
 SHOWN IN A 3/4 INCH CONDUIT, YET THIS
 CONDUIT IS OVER FILLED BASED ON TABLES
 FOR CONDUIT FILL IN CHAPTER 9
 250.110,250.122,680.6, 680.25B
  
 *** IMPORTANT**
 4) NOTE: PLEASE SEE ZONING NOTES, AND
 PLEASE SEE THAT IT IS KNOWN BY THIS
 OFFICE THAT THE EXISTING ELECTRICAL
 METER IS BEING MOVED, HOWEVER THE
 EXISTING ELECTRICAL SERVICE PANEL IS
 REMAINING WHERE IT IS AND DOES NOT MEET
 MIN CLEARENCE REQUIREMENTS PER NEC. 680.
 PLEASE KNOW, THE EXISTING ELECTRICAL
 PANEL MUST BE MOVED.
  
 ** PLEASE KNOW, EACH PLAN, PANEL
 SCHEDULE ETC SHALL BE SPECIFIC IN DESIGN
 TO EACH DWELLING/LOCATION AND POOL BEING
 DESIGNED.
 106.1.1,1.6.1.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  