Plan Review Notes
Plan Review Notes For Permit 06061300
Permit Number 06061300
Review Stop E
Sequence Number 1
Notes
Date Text
2006-06-28 00:00:00**** UNSAT ****
  
 1) NOTE: PLEASE PROVIDE LOAD ON EXISTING
 SERVICE W/ NEW LOAD ADDED.
 220.31, 215.5
  
 2) NOTE: PLEASE SEE NEW 1/2 HP PUMP IS
 SHOWN WITH THREE #8'S ON PLANS AND ON
 "PANEL SCHEDULE" PROVIDED BY THE
 ELECTRICAN. PLEASE SEE THE MAX OPC FOR
 1/2 HP PUMP SHALL BE SIZED FROM NEC
 430.31,32,430.148
 PLEASE ALSO SEE 3-#8'S WILL NOT FIT INTO
 THIS PUMP, OR RATED FOR CONNECTION TO
 30A OR 20A BRKR.
 PLEASE REVISE AND ADJUST CONDUCTOR SIZES
 ON PLANS AND SHEET ATTACHED TO PLANS.
  
 3) NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM EXISTING
 SERVICE TO NEW SUB/POOL PANEL.
 250.110,250.122,680.6, 680.25B
  
 ** PLEASE KNOW, EACH PLAN, PANEL
 SCHEDULE ETC SHALL BE SPECIFIC IN DESIGN
 TO EACH DWELLING/LOCATION AND POOL BEING
 DESIGNED.
 106.1.1,1.6.1.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  