Plan Review Notes
Plan Review Notes For Permit 06061290
Permit Number 06061290
Review Stop B
Sequence Number 1
Notes
Date Text
2006-06-23 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06061290
 ADD: 6501 N JOG RD
 CONT:ALL-SITE CONSTRUCTION, INC
 TEL: (561)718-9542
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 --- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
  
 2) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WILL BE ISSUED.NOTE:
 2004 FLORIDA BUILDING CODE
 2004 EXISTING BUILDING CODE
 A)(1) CLASSIFICATION OF WORK,
 LEVEL-1
 LEVEL-2
 LEVEL-3
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 3)302.1.1.1 SEPARATION.
 WHERE TABLE 302.1.1 REQUIRES A
 FIRE-RESISTANCE-RATED SEPARATION, THE
 INCIDENTAL USE AREA SHALL BE SEPARATED
 FROM THE REMAINDER OF THE BUILDING WITH
 A FIRE BARRIER. WHERE TABLE 302.1.1
 PERMITS AN AUTOMATIC FIRE-EXTINGUISHING
 SYSTEM WITHOUT A FIRE BARRIER, THE
 INCIDENTAL USE AREA SHALL BE SEPARATED
 BY CONSTRUCTION CAPABLE OF RESISTING THE
 PASSAGE OF SMOKE. THE PARTITIONS SHALL
 EXTEND FROM THE FLOOR TO THE UNDERSIDE
 OF THE FIRE-RESISTANCE-RATED
 FLOOR/CEILING ASSEMBLY OR
 FIRE-RESISTANCE-RATED ROOF/CEILING
 ASSEMBLY OR TO THE UNDERSIDE OF THE
 FLOOR OR ROOF DECK ABOVE. DOORS SHALL BE
 SELF-CLOSING OR AUTOMATIC-CLOSING UPON
 DETECTION OF SMOKE. DOORS SHALL NOT HAVE
 AIR TRANSFER OPENINGS AND SHALL NOT BE
 UNDERCUT IN EXCESS OF THE CLEARANCE
 PERMITTED IN ACCORDANCE WITH NFPA 80.
 302.1.1
 ROOM OR AREA
 STATIONARY LEAD-ACID BATTERY SYSTEMS
 HAVING A LIQUID CAPACITY OF MORE THAN
 100 GALLONS USED FOR FACILITY STANDBY
 POWER, EMERGENCY POWER OR UNINTERRUPTED
 POWER SUPPLIES.
 SEPERATION(A)
 1-HOUR FIRE BARRIERS AND FLOOR/CEILING
 ASSEMBLIES IN GROUP B, F, H, M, S AND U
 OCCUPANCIES. 2-HOUR FIRE BARRIERS AND
 FLOOR/CEILING ASSEMBLIES IN GROUP A, E,
 I AND R OCCUPANCIES.
 (A). WHERE AN AUTOMATIC
 FIRE-EXTINGUISHING SYSTEM IS PROVIDED,
 IT NEED ONLY BE PROVIDED IN THE
 INCIDENTAL USE ROOM OR AREA.
  
 4) MEZZANINE LEVEL WHAT IS THE POSTED
 FLOOR LOAD, WHAT IS THE LOAD OF NEW
 STRUCTURE PLUS THE LOAD OF THE BATTERIES
 PER SQUARE FOOT.
 106.4.2 STORAGE & FACTORY- INDUS-
 TRIAL OCCUPANCIES. IT SHALL BE THE
 RESPONSIBILITY OF THE OWNER, AGENT,
 PROPIETOR OR OCCUPANT OF GROUP S AND
 GROUP F OCCUPANCIES, OR ANY OCCUPANCY
 WHERE EXCESSIVE FLOOR LOADING IS LIKELY
 TO OCCUR, TO EMPLOY A COMPETENT ARCHI-
 TECT OR ENGINEER IN COMPUTING THE SAFE
 FLOOR LOAD CAPACITY. ALL SUCH COMPUTA-
 TIONS SHALL BE ACCOMPANIED BY AN AFFA-
 DAVIT FROM THE ARCHITECT OR ENGINEER
 STATING THE SAFE ALLOWABLE FLOOR LOADS
 ON EACH FLOOR IN POUNDS PER SQ FT.THE
 COMPUTATIONS & AFFADAVIT SHALL BE FILED
 AS A PERMANENT RECORD OF THE BLDG DEPT.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  