Date Text
2006-07-24 00:00:00*** DENIED***HYDRAULIC CALCULATION
 WITH SAFETY MARGIN OF 4.414
 UNACCEPTABLE.RECALCULATE TO PROVIDE
 SAFETY MARGIN OF AT LEAST 5.0