Plan Review Notes For Permit 06061179 |
Permit Number |
06061179 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-06-26 00:00:00 | DENIED | | | | 1) SPECIFY THE BUILDINGS CONSTRUCTION | | TYPE, BUILDING OCCUPANCY, HEIGHT, NUMBER | | OF STORIES, SPRINKLERED OR NOT, OCCUPANT | | LOAD FOR THE FLOOR AND ALTERATION | | LEVEL(EXISTING BUILDING CODE). USE 2004 | | FBC DESIGNATIONS. FBC 106.1.1* | | | | 2) INDICATE THE LOCATIONS OF THE | | EXISTING FIRE RATED PARTITIONS. FBC | | 106.1.2. | | | | 3) THE NEW RECEPTION COUNTER IS REQUIRED | | TO BE ACCESSIBLE. PROVIDE DETAILS | | SHOWING COMPLIANCE WITH FBC 11-7.2. | | | | 4) DOORS AND HARDWARE SHALL COMPLY WITH | | ACCESSIBILITY REQUIREMENTS OF FBC | | 11-4.13. | | | | 5) FLOOR SURFACES AND CHANGES IN LEVEL | | IN ACCESSIBLE AREAS SHALL COMPLY WITH | | FBC 11-4.5. | | | | 6) ALTERATIONS TO THE PRIMARY FUNCTION | | AREA MUST COMPLY WITH FBC 11-4.1.6. | | | | 7)A RECORDED COPY OF THE NOTICE OF | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | PERMIT CAN BE ISSUED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 |
|