Plan Review Notes
Plan Review Notes For Permit 06061149
Permit Number 06061149
Review Stop E
Sequence Number 2
Notes
Date Text
2006-07-15 00:00:00*** UNSAT 2ND REVIEW **
  
 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS
 REVIEW.
 PLEASE SEE RISER DIAGRAM IS NOT COMPLETE
 AND DOES NOT CONTAIN INFORMATION AS
 PREVIOUSLY NOTED.
 250.50,110.9, 250.110, 250.122, 250.24B
 ETC
  
 2) NOTE: PLEASE SEE PLANS NOW INCLUDE A
 NEW SUB PANEL NOT IN SCOPE OF WORK ON
 PERMIT APPL.
 PLEASE NOTE THE LOCATION OF THIS PANEL
 AS IT WILL BE REQUIRED TO MEET 110.26,
 240.24, 408.7
  
 3) NOTE: PLEASE SEE FBC ADMIN SECT
 106.1.3, PLANS MAY NOT BE DRAW IN
 PENCIL. THESE MUST BE PHOTO-COPIED
 BEFORE SUBMITTING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  