2006-06-29 00:00:00 | ******DENIED****** |
| REFERENCE: FBC-2004 FUEL GAS |
| |
| THE FOLLOWING INFORMATION IS REQUIRED |
| FOR PLAN REVIEW FOR A GAS PERMIT: |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. |
| 2. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, AND ALL PIPE SIZES. |
| 3. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4).(NOTE: THE |
| LONGEST RUN INDICATED ON DRAWING IS |
| INCORRECT, AND THE PIPE SIZING IS WRONG |
| PER FBC-2004 FUEL GAS TABLES 402.4(2), |
| AND 402.4(20). SYSTEM MIGHT NEED TO GO |
| TO A 2LB SYSTEM WITH REGULATORS, PLEASE |
| CORRECT FOR RESUBMITTAL) |
| |
| **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED, AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. PLEASE SEE MARKED UP DRAWING IN |
| RED INK, AND ATTACHED SIZING TABLESFOR |
| REFERENCE FOR RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |