2006-09-11 00:00:00 | ***UNSAT3RD REVIEW *** |
| |
| ** PLEASE SEE NOTE BELOW ARE TAKEN |
| DIRECTLY FROM THE TOW PREVIOUS REVIEWS. |
| PLEASE SEE FS 553.80(2) (B) WITH RESPECT |
| TO REPEAT CODE COMPLIANT COMMENTS AS 4X |
| FEE FOR PLAN REVIEW WILL BE ASSESSED AS |
| REQUIRED. |
| PLEASE BE SURE TO ADDRESS ALL COMMENTS. |
| PLEASE SEE NEW COMMENTS THE PLANS/LOAD |
| CALCS ETC THAT WERE SUBMITTED. |
| |
| 1) NOTE: NO, PLEASE SEE PREVIOUS NOTES |
| BELOW FROM TWO PREVIOUS REVIEW. |
| |
| ** PLEASE SEE NO ELECTRICAL DETAIL |
| SUBMITTED FOR NEW WIRING, CONDUCOTRS, |
| CONDUITS, DISCONNECTS, GFI RECETPS, |
| PANEL SCHEDULE INDICATING NEW A/C LOADS, |
| LOAD CALCULATIONS, AND SIZE OF EXSITING |
| SERVICE. |
| 215.5,210.63,440.11,210.70,240.4,310.16, |
| 220.31B ETC |
| |
| *** NEW NOTE *** |
| |
| 2) NOTE: PLEASE SEE LOAD CALCUALITONS |
| SUBMITTED DO NOT COMPLY WITH 220.31B AS |
| PREVIOUSLY NOTED. |
| PLEASE SEE CALCULATION IN FACT DO NOT |
| SHOW ANY AHU HEAT (LARGER THAN COOLING ) |
| LOADS.?? |
| 220.21, 220.31B |
| |
| 3) NOTE: PLEASE SEE NO OCP IS SHOWN FOR |
| NEW A/C SYSTEM AS REQUESTED. |
| 240.4,440.11,310.16, 240.21, 424.3B |
| |
| 4) NOTE: PLEASE SEE #10'A ARE NOT RATED |
| FOR THE 10KW LOAD OF THE HEAT IN THE |
| AHU.. |
| PLEASE KNOW IF THERE ARE TWO SEPARATE |
| FEEDS TO THE CU AND AHU, THEN PLEASE |
| SHOW EACH. |
| 424.3B, 240.4,310.16 ETC |
| |
| 5) NOTE: PLEASE SEE MISSING LOCATIONS OF |
| UNITS AND DISONNECT ON PLANS. |
| 240.24,110.26,440.11 ETC |
| |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |