Plan Review Notes
Plan Review Notes For Permit 06060985
Permit Number 06060985
Review Stop E
Sequence Number 1
Notes
Date Text
2006-06-27 00:00:00***** UNSAT ***
  
 1) NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM EXISTING
 SERVICE TO NEW PANEL.
 250.110,250.122, 680.6
  
 2) NOTE: PLEASE PROVIDE LOAD
 CALCULATIONS AND PANEL SCHEDULE OF
 EXISTING SERVICE WHICH INDICATE THE NEW
 OCP FOR POOL PANEL AND NEW LOAD ADDED TO
 EXISTING LOAD.
 408.4,220.31
 ** PLEASE KNOW, THIS MAY BE PROVIDED BY
 THE ELECTRICAL CONTRACTOR AND IS NOT
 REQUIRED BY CURTIS- SINCLAIR.
  
  
 3) NOTE: PLEASE VERIFY 3-#10'S TO 1HP
 POOL PUMP. *THIS IS OK, HOWEVER VERIFY
 AS IF PLANS INDICATE #10, THEN THESE
 WILL BE REQUIRED.
 215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  