Plan Review Notes For Permit 06060983 |
Permit Number |
06060983 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-08-14 00:00:00 | ***** REDLINED NOTES** | | | | PLEASE SEE 424.3B FOR MIN OCP FOR AHU | | HEAT, @ 125%. (MIN) | | PREVIOUS REVIEW> | | | | PLEASE SEE A REVISED PANEL SCHEDULE WILL | | BE NEED TO BE SUBMITTED BEFORE FINAL. | | ALL OTHER REVISIONS REQUIRED BEFORE | | ROUGH. | | |
|