Plan Review Notes For Permit 06060983 |
Permit Number |
06060983 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-06-21 00:00:00 | *** DENIED *** | | 1) ENERGY CALCULATIONS NEED TO BE SIGNED | | BY OWNER/AGENT, PER 2004 FBC | | 13-600.3.ABC.2 . | | | | 2) PLEASE SUBMIT A COMPLETEMANUAL J | | CALCULATIONS, SHOWING CFM'S AND DUCT | | SIZES TO EACH ROOM, PER 2004 FBC | | 13-607.1.ABC.1 ; OR A MANUAL D | | CALCULATION, PER 2004 FBC/R M1601.1 . | | | | 3) PLEASE CORRECT SUPPLY AIR DUCT SIZES | | ON PLANS ACCORDING TO THE MANUAL J | | CALCULATIONS. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. | | |
|