2006-07-28 00:00:00 | **** UNSAT **** |
| |
| |
| ** PLEASE SEE SOME NOTE FROM PREVIOUS |
| REVIEW AND SOME NEW NOTES. |
| |
| 1) NOTE: NO, SAME, ONLY CONTAINS A |
| PRINTED NAME. PLEASE KNOW,PLANS SHALL BE |
| SIGNED BY THE PERSON WITH THE PRINTED |
| NAME. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE BE SURE THE PRINTED NAME |
| AND SIGNATURE IS ON PLANS FOR THE PERSON |
| REPSONSIBLE FOR PLANS. |
| FBC 106.2.1 |
| |
| 2) NOTE:NO, UNCLEAR AS THE FLOOD |
| ELEVATION COULD NOT BE FOUND. AN ELEV OF |
| 6.02 IS SHOWN BUT IT IS UNCLEAR WHAT |
| THIS IS. ? |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE KNOW, LOCATION OF |
| HOUSE/GEN IS IN A "A" FLOOD ZONE AND |
| PLANS SHALL INDICATE EQUIPMENT AT 6" |
| MIN ABOVE THE BFE. |
| |
| 3) NOTE: NO, THE LAYOUT IS STILL UNCLEAR |
| AS SITE PLANS SHOW THE NEW EM PANEL |
| OUTSIDE AND THE PTHER PANELS INSIDE. |
| PLEASE SEE SPECS INDICATE THE EM PANEL |
| AS NEMA 1 AND PLANS PLACE THIS PANEL |
| OUTSIDE?? |
| PLEASE ALSO KNOW THAT THE DISCONNECTING |
| MEANS FOR THE FEEDERS COMING FROM THE |
| GEN SHALL BE GROUPED WITH THE EXISTING |
| MAIN(S). 225.34, 230.72 |
| PLEASE INDICATE THE OCP FEEDIGN THE EM |
| PANEL. PLEASE CLARIFY THE 200 A MAIN. IT |
| IS BEING ASSUMED IT IS A MCB PANEL? |
| 240.4,310.16,110.3,90.7, ETC |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE PROVIDE A LAYOUT FOR ALL |
| EQUIPMENT AS VERIFICATION OF THE |
| GROUPING OF THE MAINS AND DISCONECT CAN |
| NOT BE DONE AT THIS TIME. |
| 230.72,225.34 |
| |
| ** SAME NOTE, NO SLAB DETAIL PROVIDED |
| FOR GEN UNIT. |
| |
| ** PREVIOUS NOTE ** |
| PLEASE SEE BLDG COMMENTS AS SLAB DETAIL |
| FOR GEN IS MISSING. |
| |
| ** NEW NOTE ** |
| |
| 1) NOTE: PLEASE SEE FS 553.80(2)(B) WITH |
| RESPECT TO DESIGN PROFESSIONALS |
| RESPONSIBLE FOR PLANS AND REPEAT |
| COMMENTS FOR CODE COMPLIANCE. |
| THIS IS ONLY GIVEN AS A NOTICE AT THIS |
| TIME. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |