Plan Review Notes
Plan Review Notes For Permit 06060909
Permit Number 06060909
Review Stop E
Sequence Number 1
Notes
Date Text
2006-06-23 00:00:00**** UNSAT ****
  
  
 1) NOTE: PLEASE BE SURE THE PRINTED NAME
 AND SIGNATURE IS ON PLANS FOR THE PERSON
 REPSONSIBLE FOR PLANS.
 FBC 106.2.1
  
 2) NOTE: PLEASE KNOW, LOCATION OF
 HOUSE/GEN IS IN A "A" FLOOD ZONE AND
 PLANS SHALL INDICATE EQUIPMENT AT 6"
 MIN ABOVE THE BFE.
  
 3) NOTE: PLEASE PROVIDE A LAYOUT FOR ALL
 EQUIPMENT AS VERIFICATION OF THE
 GROUPING OF THE MAINS AND DISCONECT CAN
 NOT BE DONE AT THIS TIME.
 230.72,225.34
  
 PLEASE SEE BLDG COMMENTS AS SLAB DETAIL
 FOR GEN IS MISSING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  