Plan Review Notes For Permit 06060899 |
Permit Number |
06060899 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-08-11 00:00:00 | DENIED; | | 1.WHAT TYPE OF WORK WILL BE DONE IN THE | | WORK ROOM AND WHY IS A REFRIGERATOR | | REQUIRED? | | 2. MEN'S ROOM IS NOT HANDICAP COMPLIANT. | | A)DOOR SWINGS INTO CLEAR FLOOR SPACE | | OF THE LAVITORY. | | B) THE URINAL AND LAVATORY IN THE | | | | HANDICAP BATHROOM MUST MEET ALL | | THE REQUIREMENTS OF CHAPTER 11. | | URINAL TO COMPLY WITH SECTIONS | | 11-4.18.2 THRU 11-4.18.4. | | LAVATORY TO COMPLY WITH SECTIONS | | 11-4.19.1 THRU 11-4.19.6. | | 3. A WATER HEATER IS SHOWN ON PAGE 2 | | (FLOOR PLAN) BUT NO HOT WATER PIPING IS | | SHOWN ON WATER RISER DIAGRAM. PLEASE | | NOTE ON PLANS IF NEW BATHROOM WILL NOT | | HAVE HOT WATER TO THE LAV. | | 4.CUP DISPENSOR REQUIRED AT DRINKING | | FOUNTAINS. CHAPTER 11 SECTION | | 11-4.1.3(10). PLEASE ADD NOTE ON PLANS. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|