2006-08-05 00:00:00*** UNSAT 2ND REVIEW ***
  
 1) NOTE: PLEASE SEE NOTE FROM PREVIOUS
 REVIEW. PLEASE SEE FBC CHAPTER 13, AS
 THE SPACE IS IN A BUILDING LARGER THAN
 5K SQ FT. PLEASE SEE 13-415.1.ABC.1.1,
 .1.2, .1.3.
 THIS SPACE IS NOT A BUILDING. PLEASE SEE
 ELECTRICAL IS FED FROM A SERVICE WHICH
 FEEDS ONE BUILDING. PLEASE SEE FBC
 DEFINITIONS OF BUILDINGS. IF THIS SPACE
 WAS SEPARATED BY A "FIRE WALL" ON BOTH
 SIDES WHICH REQUIRES 4HR SEPARATION AND
 ALSO REQUIRES COMPLETE COLLAPSE OF THE
 ADOINING ROOFS WITH OUT AFFECTTING THE
 STRUCTURAL INTEGRITY OF THE BUILDING
 ETC.
 PLEASE SEE AT THIS POINT THE SPACE WOULD
 BE CONSIDERED A BUILDING AND A SEPARATE
 ELECTRICAL SERVICE WOULD BE REQUIRED.
  
 ** PLEASE SEE SPACE #11&12 SEEM TO BE
 EXISTINGWITH ONLY THE NEW SEPARATION
 BEING ADDED, IF SO PLEASE LABEL ALL
 ELECTRICAL OR CLOUD SPACE AS EXISTING.
 PLEASE SEE SPACE #13&14 WILL REQUIRE NEW
 CONTROLS PER CHAPTER 13 AS NOTED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  