2006-08-05 00:00:00 | *** UNSAT 2ND REVIEW *** |
| |
| 1) NOTE: PLEASE SEE NOTE FROM PREVIOUS |
| REVIEW. PLEASE SEE FBC CHAPTER 13, AS |
| THE SPACE IS IN A BUILDING LARGER THAN |
| 5K SQ FT. PLEASE SEE 13-415.1.ABC.1.1, |
| .1.2, .1.3. |
| THIS SPACE IS NOT A BUILDING. PLEASE SEE |
| ELECTRICAL IS FED FROM A SERVICE WHICH |
| FEEDS ONE BUILDING. PLEASE SEE FBC |
| DEFINITIONS OF BUILDINGS. IF THIS SPACE |
| WAS SEPARATED BY A "FIRE WALL" ON BOTH |
| SIDES WHICH REQUIRES 4HR SEPARATION AND |
| ALSO REQUIRES COMPLETE COLLAPSE OF THE |
| ADOINING ROOFS WITH OUT AFFECTTING THE |
| STRUCTURAL INTEGRITY OF THE BUILDING |
| ETC. |
| PLEASE SEE AT THIS POINT THE SPACE WOULD |
| BE CONSIDERED A BUILDING AND A SEPARATE |
| ELECTRICAL SERVICE WOULD BE REQUIRED. |
| |
| ** PLEASE SEE SPACE #11&12 SEEM TO BE |
| EXISTINGWITH ONLY THE NEW SEPARATION |
| BEING ADDED, IF SO PLEASE LABEL ALL |
| ELECTRICAL OR CLOUD SPACE AS EXISTING. |
| PLEASE SEE SPACE #13&14 WILL REQUIRE NEW |
| CONTROLS PER CHAPTER 13 AS NOTED. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |