2006-06-21 00:00:00****** UNSAT *****
  
 1) NOTE: PLEASE SEE PERMIT APPLICATION
 MENTIONS TO SPLIT FOUR BAYS DOWN TO TWO,
 HOWEVER FROM WHAT THE PLASN INDICATE,
 THERE IS ONLY ONE BAY EXISTING WHICH IS
 NOW BEING SEPARATED BY NEW PROPOSED
 TENANT SEPARATION WALL INTO TWO NEW
 BAYS.???
 PLEASE VERIFY.
 IT WAS NOTED THAT THE UNITS MAY HAVE
 BEEN LABELED 11,12,13 AND 14, HOWEVER
 NEW SUITES MAY BE ASSIGNED.
  
 2) NOTE: PLEASE SUBMIT LOADS ON EXISTING
 SERVICES WITH NEW LOADS ADDED.
 220, 215.5
  
 3) NOTE: PLEASE SEE FBC CHAPTER 13 ,
 13-415.1.ABC.1.1,.1.2,.1.3
 13-415.1.AB.1, 13-415.2.ABC.1
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717