Plan Review Notes
Plan Review Notes For Permit 06060867
Permit Number 06060867
Review Stop B
Sequence Number 2
Notes
Date Text
2006-07-10 00:00:00DENIED
  
 1) THE ROOFING SYSTEM SPECIFIED ON PAGE
 40 OF THE MULE-HIDE PRODUCT NOA HAS A
 MAXIMUM DESIGN PRESSURE OF -60 PSF. THIS
 PRESSURE IS TO LOW FOR ZONE 3 (CORNERS).
 GENERAL LIMITATION #7 ON PAGE 43 OF THE
 NOA ALLOWS THE CORNERPRESSURES TO BE
 INCREASED BY INCREASING THE FASTENER
 DENSITIES USING THE CALCULATIONS
 SPECIFIED IN (RAS 117) ROOFING
 APPLICATION STANDARD 117. HOWEVER,
 GENERAL LIMITATION #7 ON THIS NOA
 REQUIRES THESE RAS 117 CALCULATIONS TO
 BE PREPARED, SIGNED AND SEALED BY A
 FLORIDA REGISTERED ENGINEER, ARCHITECT
 OR REGISTERED ROOF CONSULTANT. PLEASE
 SUBMIT TWO COPIES OF SIGNED AND SEALED
 RAS 117 CALCULATIONS FOR THIS SYSTEM.
  