2 |
|
Notes |
Date |
Text |
2006-07-10 00:00:00 | DENIED | | | | 1) THE ROOFING SYSTEM SPECIFIED ON PAGE | | 40 OF THE MULE-HIDE PRODUCT NOA HAS A | | MAXIMUM DESIGN PRESSURE OF -60 PSF. THIS | | PRESSURE IS TO LOW FOR ZONE 3 (CORNERS). | | GENERAL LIMITATION #7 ON PAGE 43 OF THE | | NOA ALLOWS THE CORNERPRESSURES TO BE | | INCREASED BY INCREASING THE FASTENER | | DENSITIES USING THE CALCULATIONS | | SPECIFIED IN (RAS 117) ROOFING | | APPLICATION STANDARD 117. HOWEVER, | | GENERAL LIMITATION #7 ON THIS NOA | | REQUIRES THESE RAS 117 CALCULATIONS TO | | BE PREPARED, SIGNED AND SEALED BY A | | FLORIDA REGISTERED ENGINEER, ARCHITECT | | OR REGISTERED ROOF CONSULTANT. PLEASE | | SUBMIT TWO COPIES OF SIGNED AND SEALED | | RAS 117 CALCULATIONS FOR THIS SYSTEM. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | |
|