 DENIED
  
 1) THE PRESSURES THAT ARE STATED IN
 INSTALLATION SCHEDULE ARE HIGH AND THE
 SHUTTER SPANS AT THOSE PRESSURES MAX OUT
 BELOW WHAT YOU REQUIRE (SEE SHUTTER #3
 AT 13'-7" AND #12 AT 12'-9")
  
 2) PROVIDE TOP AND BOT MOUNT # ON
 INSTALLATION SCHEDULE FOR EACH SHUTTER
 TO BETTER SEE MAX ANCHOR SPACING
  
 BLDG PLAN REVIEW