Plan Review Notes For Permit 06060856 |
Permit Number |
06060856 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-07-03 00:00:00 | | | | | DENIED | | | | 1) THE PRESSURES THAT ARE STATED IN | | INSTALLATION SCHEDULE ARE HIGH AND THE | | SHUTTER SPANS AT THOSE PRESSURES MAX OUT | | BELOW WHAT YOU REQUIRE (SEE SHUTTER #3 | | AT 13'-7" AND #12 AT 12'-9") | | | | 2) PROVIDE TOP AND BOT MOUNT # ON | | INSTALLATION SCHEDULE FOR EACH SHUTTER | | TO BETTER SEE MAX ANCHOR SPACING | | | | BLDG PLAN REVIEW | | ADRIAN MORSE | | 561-805-6716 |
|