Date |
Text |
2007-02-11 18:38:38 | ** UNSAT ** |
| |
| 1) NOTE: PLEASE SEE PREVIOUS ZONING REVIEW COMMENTS AS |
| SCREENING DOES SEEM TO HAVE BEEN SUBMITTED. |
| |
| 2) NOTE: PLEASE SEE GENERATOR LOAD SUMMARY ON E5.1 |
| WHICH SHOWS HQ ON LOAD SUMMARY. IS THIS ANOTHER UNIT OR |
| IS THIS EQ? THIS SEEMS TO HAVE BEEN A MISPRINT AND MAY |
| HAVE BEEN REDLINED, HOWEVER AS THE PLANS AND RISER HAVE |
| BEEN COMPLETELY REVISED ON SO MANY OCCASIONS, THIS IS |
| NOT BEING ASSUMED. |
| |
| 3) NOTE: PLEASE SEE THE LOAD ON EMDP IS NOT THE SAME |
| LOAD AS SHOWN ON MDP2 FOR THE SAME ? |
| PLEASE CORRECT AND CORRELATE. |
| 220, 215.5, 240.4, 310.16 ETC |
| FBC 106.1.2 |
| |
| 4) NOTE: PLEASE SEE A 4X FEED WAS ASSESSED FOR THE |
| INSTALLATION OF GENERATOR/ GAS /ELECTRICAL ETC. |
| A FEE OF $6300 IS NOW DUE. |
| |
| 5) NOTE: PLEASE SEE THE NOTICE OF COMMENCEMENT |
| SUBMITTED WILL BE REQUIRED TO BE RE-RECORDED AND |
| SUBMITTED BEFORE PICKING UP PERMIT AS IT HAS BECOME |
| VOID PER FS 713.13(2). THIS IS INFORMATION GIVEN AT |
| THIS TIME. |
| |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |