Plan Review Notes For Permit 06060723
Permit Number 06060723
Review Stop E
Sequence Number 3
Notes
Date Text
2007-01-13 17:29:32** UNSAT 3RD REVIEW**
  
  
 ** PLEASE SEE COMMENTS BELOW ARE BASED ON THE REVISED
 PLANS SUBMITTED.
 ** PLEASE SEE AS REQUESTED ON THE PREVIOUS REVIEW, NO
 PREVIOUS REVIEWED ORIGINAL PLANS WERE SUBMITTED FOR
 REFERENCE. PLEASE SUBMIT ONE SET OF EACH OF THE
 PREVIOUS PLANS.
  
 1) NOTE:PLEASE SUBMIT TWO SETS OF PLANS WITH ALL
 SHEETS PLACED INTO SETS AND SHEETS ATTACHED.
 PLEASE SEE MORE THAN TWO SETS OF MANUFACTURES SPEC/CUT
 SHEETS WERE SUBMITTED AND EACH OF THESE CONTAIN
 DIFFERENT SHEETS. PLEASE SUBMIT ONLY THE TWO SETS NEED
 FOR REVIEW OF SAID SHEETS.
 106.1.2, 106.1.
  
 ***PLEASE SEE COORDINATION BETWEEN THE RISER, LOADS AND
 PANELS NEED TO BE ADDRESSED.
 THE COMMENTS BELOW ARE BEING NOTED, HOWEVER DUE TO THE
 NEW REVISED RISER AND THE AMOUNT OF NEEDED CHANGES
 THERE MAY BE NEW COMMENTS ON THE NEXT REVIEW.
  
 2) NOTE:
 A) PLEASE SEE MDP2-8 SHOWS A 400A BREAKER FEEDING WHAT
 IS LABELED ATS-EQ.
 PLEASE SEE THE LOAD ON THIS IS BEING SHOWN AS
 34.7/35.1/34.5 WHICH IS THE LOAD SHOWN ON PANEL HEQ.
 B) PLEASE SEE HOWEVER RISER IS NOW SHOWING THE MDP3
 BEING FED FROM THE ATS-EQ NOW WITH OUT ANY LOAD
 CONSIDERATION BEING SHOWN. PLEASE SEE THE LOAD ALONE
 BEING SHOWN ON MDP3 IS 416.7 KVA WHICH IS NOT ON MDP2
 OR IN THE GENERATOR LOAD SUMMARY.
 PLEASE CORRELATE THE GENERATOR LOAD SUMMARY WITH ALL
 LOADS.
 C) PLEASE SEE THE RISER NOW SHOWS A 175AMP DISCONNECT
 BEING INSTALLED FROM THE ATS EQ TO THE MDP3? HOW IS IT
 POSSIBLE FOR THIS TO BE 175AMPS WHEN THE LOAD UNDER
 NORMAL EXCEEDS THAT OF THIS EQUIPMENT? PLEASE SEE THE
 NOTE ABOVE AS ONCE AGAIN, NO LOADS FOR THE MDP3 IS
 BEING SHOWN AS PART OF THE LOAD ON THE GENERATOR, YET
 IT IS BEING SHOWN CONNECTED TO THIS SYSTEM.
 D) PLEASE CLEAR UP RISER AND WHETHER OR NOT THE MDP3 IS
 FED FROM THE SAME BREAKER THAT IS BEING SHOWN FOR
 ATS-EQ AND HEQ. IF THE HEQ IS FED FROM THE 400A BREAKER
 ON MDP2 THIS IS FINE HOWEVER THE ADDITION OF THE NEW
 MDP3 HAS CREATED AN ENTIRE NEW LIST OF COMMENTS.
 E) PLEASE SEE BASED ON THE ADDITION OF MDP3 ON THE
 RISER, THE FEEDERS BEING SHOWN AS ATS-2 AND ATS-3 ARE
 NOT SUFFICIENT UNDER NORMAL OR LOADS UNDER EMERGENCY.
 HOW CAN THE NORMAL SIDE OR THE EMERGENCY SIDE INDICATE
 CONDUCTORS LESS THAN THE LOAD AS SHOWN?
  
 240.4, 310.16, 230.70, 220, 240.21, 215.5, 215.3,
 230.42, 230.79, 225.39 ETC.
 PLEASE KNOW THERE ARE NUMEROUS SECTIONS WHICH COULD BE
 NOTED.2002 NEC
 PLEASE REVISE RISER AND COORDINATE ALL.
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]