2006-12-01 07:27:29DENIED:
 COMMENTS FROM REVIEW DATED 10-28-06:
  
 COMMENT 1:REQUEST FOR CLEARANCES TO THE PROPERTY
 LINE, ADJACNT BUIDLINGS, FRESH AIR INTAKES, DOORS,
 WINDOWS, LOUVERS, ETC.RESPONSE INDICATES REVISED
 DRAWING PROVIDE THIS INFORMATION. THE ONLY DIMENSION
 PROVIDED IS ON PLAN SHEET E3.1 WHICH INDICATES 6 FEET
 FROM THE BUILDING.PER 2004 FMC 401.5.1, FRESH AIR
 INTAKES SHALL NOT BE LOCATED CLOSER THAN 10 FEET FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT.
  
 COMMENT 2:INDICATE IF PROTECTION FROM DAMAGE IS
 REQUIRED IN ACCORDANCE WITH 2004 FMC 401.5.RESPONSE
 INDICATES "SEE REVISED DRAWINGS".PLANS DO NOT
 INDICATE ANY PROTECTION OR ANNOTATE HOW THIS IS
 ACCOMPLISHED.
  
 COMMENT 3:OKAY.
 **************NEW COMMENT***********
  
 1.PLAN SHEET E0.1 GENERATOR SPECIFICATIONS, REVISION
 INDICATES THE SUB-BASE FUEL TANK AS 540 GAL & THE
 SUBMITTAL ON THE GENERAC POWER SYSTEM DWG OE7823,
 INDICATES THE TANK CAPACITY AS 706 GAL.PLEASE
 CORRELATE.
  