Plan Review Notes For Permit 06060723 |
Permit Number |
06060723 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-12-01 07:27:29 | DENIED: | | COMMENTS FROM REVIEW DATED 10-28-06: | | | | COMMENT 1:REQUEST FOR CLEARANCES TO THE PROPERTY | | LINE, ADJACNT BUIDLINGS, FRESH AIR INTAKES, DOORS, | | WINDOWS, LOUVERS, ETC.RESPONSE INDICATES REVISED | | DRAWING PROVIDE THIS INFORMATION. THE ONLY DIMENSION | | PROVIDED IS ON PLAN SHEET E3.1 WHICH INDICATES 6 FEET | | FROM THE BUILDING.PER 2004 FMC 401.5.1, FRESH AIR | | INTAKES SHALL NOT BE LOCATED CLOSER THAN 10 FEET FROM | | ANY HAZARDOUS OR NOXIOUS CONTAMINANT. | | | | COMMENT 2:INDICATE IF PROTECTION FROM DAMAGE IS | | REQUIRED IN ACCORDANCE WITH 2004 FMC 401.5.RESPONSE | | INDICATES "SEE REVISED DRAWINGS".PLANS DO NOT | | INDICATE ANY PROTECTION OR ANNOTATE HOW THIS IS | | ACCOMPLISHED. | | | | COMMENT 3:OKAY. | | **************NEW COMMENT*********** | | | | 1.PLAN SHEET E0.1 GENERATOR SPECIFICATIONS, REVISION | | INDICATES THE SUB-BASE FUEL TANK AS 540 GAL & THE | | SUBMITTAL ON THE GENERAC POWER SYSTEM DWG OE7823, | | INDICATES THE TANK CAPACITY AS 706 GAL.PLEASE | | CORRELATE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | AT (561)805-6719 OR E-MAIL [email protected]. |
|