2006-11-20 09:02:28 | *** UNSAT 2ND REVIEW *** |
| |
| |
| *** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH IS |
| STILL IN NEED OF ADDRESSING. PLEASE ALSO WEE NOTES |
| WHICH ARE NEW BASED ON REVISED ITEMS NOW SHOWN ON |
| PLANS. |
| |
| ** PLEASE SEE NOTES BELOW ARE TAKEN DIRECTLY FROM |
| PREVIOUS REVIEW AND MARKED WITH AN OK! , NO! (WITH |
| FURTHER EXPLANATION) OR SOME MAY BE LABELED WITH OK/NO |
| AS PART OF THE COMMENT MAY HAVE BEEN ADDRESSED ONLY. |
| |
| |
| 1) NOTE: OK. |
| |
| 2) NOTE: OK. |
| |
| 3) NOTE: OK. |
| |
| 4) NOTE: OK. |
| |
| 5) NOTE:NO, PLEASE SEE THE COMMENT AS PREVIOUSLY |
| NOTED WAS TO OBTAIN CORRECT LOCATION TO BE COORDINATED |
| WITH THE FIRE MARSHAL'S OFFICE AND SHALL BE SHOWN AND |
| NOTED ON THE PLANS THIS WAY. THE PLANS RESPONSE AND |
| "KEY NOTE" READS TO BE LOCATED WITH THE OWNER. THIS IS |
| THE DECISION OF THE FIRE MARSHAL'S OFFICE AND THE CODE |
| ONLY. PLEASE ALSO SEE CODE SECTION AS PREVIOUSLY GIVEN. |
| FOR LOCATION REQUIREMENTS |
| |
| ** PREVIOUS REVIEW NOTE REVIEW # 1 ** |
| PLEASE SEE GEN ANNUCIATOR PANEL SHALL BE LOCATED IN THE |
| FIRE COMMAND ROOM, OR LOCATION OF FACP, NEAREST POINT |
| DESIGNATED BY THE FIRE MARSHAL'S OFFICE. |
| NFPA-101 CHAPTER 11.8.5. |
| |
| 6) NOTE: OK. RESPONSE LETTER MENTIONS THERE IS A DIESEL |
| DRIVEN FIRE PUMP. |
| |
| |
| 7) NOTE: OK/ NO, |
| PLEASE SEE SPECIFICATIONS FROM THE MANUFACTURE STILL |
| INDICATE AS 706 GALLONS. RESPONSE LETTER MENTIONS THAT |
| THE TANK WILL BE BAFFLED, YET THE SPECIFICATIONS FROM |
| THE MANUFACTURE NEED TO INDICATE THIS AT THIS TIME. |
| PLEASE SEE REVIEW COMMENTS FROM OTHER TRADES. |
| |
| |
| |
| |
| 8) NOTE: OK, HOWEVER SEE NEW NOTES. |
| |
| |
| 9) NOTE:NO, PLEASE SEE PREVIOUS NOTE, AS SHOWN ON |
| PLANS, 4-POLE TRANSFER SWITCHES WILL BE REQUIRED. THIS |
| IS BASED ON THE RISER AS SHOWN. THE GENERATOR IS BEING |
| SHOWN AS SEPARETLY DERIVED, EVEN THOUGH NOTE MENTIONS |
| IT WILL NOT BE. |
| PLEASE SEE RISER. |
| |
| ** PREVIOUS REVIEW NOTE FROM REVIEW #1 ** |
| PLEASE SEE NOTES MENTIONS THAT THE GEN WILL "NOT" BE A |
| "SEPARATELY |
| DERIVED SYSTEM" YET, GENERATOR SEEMS TO |
| BE SHOWN WITH A BOND FROM THE GEN FRAME AND GROUND BAR |
| TO THE GEN WINDINGS? |
| PLEASE KNOW, IF THIS OCCURS, THEN THIS "IS" A SDS AND |
| SHALL THEN CONTAIN A |
| 4-POLE ATS'S, GE SYSTEM AND NOTED AS SO. |
| PLEASE VERIFY AND ADJUST PLANS AS NEEDED. |
| |
| 10) NOTE: NO, PLEASE SEE THIS WAS SUBMITTED; HOWEVER |
| PLEASE SEE THE SHEETS IN FACT CONTAIN RAISED SEALS OVER |
| A "PHOTO-COPIED" SIGNATURE FROM THE ENGINEER OF RECORD. |
| ( MR. ALBERT KWAN) PLEASE SEE FLORIDA STATUTES 471.025, |
| AND FLORIDA ADMINISTRATIVE CODE 61G15-23.002. PLEASE |
| KNOW THIS IS REVIEW WHETHER OR NOT COMMENT IS MADE BY |
| BUILDING REVIEW. |
| PLEASE ALSO SEE SHEET MENTIONS TO BE 6INCHES ABOVE |
| FLOOR ELEVATION HOWEVER, EQUIPMENT SHALL BE 6 INCHES |
| ABOVE THE BFE BASED ON THE 100 YR YEAR STORM SURGES |
| LEVELS OR SURGE LEVELS BASED ON A CAT 4 STORM. PLEASE |
| SEE SLOSH CHARTS ETC. |
| PLEASE SEE SECTIONS GIVEN IN PREVIOUS REVIEW NOTE. |
| |
| ** PREVIOUS REVIEW NOTE FROM REVIEW #1 ** |
| PLEASE BUILDING REVIEW COMMENTS WITH RESPECT TO THE |
| GEN SLAB DETAIL. PLEASE SEE NO DETAIL, CONNECTIONS, |
| ELEVATIONS WERE SUBMITTED. |
| PLEASE ALSO SEE NOTE MENTIONS THE GEN @ OR ABOVE BFE. |
| PLEASE KNOW, THE GEN/ ASSOCIATED EQUIPMENT SHALL BE 6" |
| ABOVE THE BFE. |
| PLEASE SEE NFPA-110 CHAPTER 7, 7.2, 7.3, |
| 7.4, 7.9 ETC. |
| ** PLEASE KNOW, DUE TO THE SIZE, WEIGHT, EPSS |
| REQUIREMENTS ETC,THE SLAB WILL BE REQUIRED TO BE |
| SIGNED, DATED AND SEALED BY AN ENGINEER. |
| FS 471.003 |
| |
| 11) NOTE:NO, SAME NOTE. |
| |
| ** PREVIOUS REVIEW NOTE FROM REVIEW #1 ** |
| PLEASE BE SURE THE ENGINEER OF RECORD SIGNS PLANS WITH |
| HIS LEGAL/EASILY RECOGNIZABLE SIGNATURE KNOWN TO THIS |
| OFFICE AND ON RECORD IN THIS OFFICE. |
| FS 471.025, FAC 61G15-23.002 |
| |
| |
| **** NEW NOTES FROM THE 2ND REVIEW *** |
| |
| 12) NOTE: PLEASE SUBMIT THE MANUFACTURE |
| SPECIFICATION/CUT SHEETS ON THE WP HOUSING FOR THE |
| GENERATOR. |
| FBC 106.1.2, |
| 110.3,90.7 |
| |
| 13) NOTE: PLEASE BE SURE EITHER PLANS OR MANUFACTURE |
| SPECIFICATIONS INDICATE THE FUEL CONSUMPTION BASED ON |
| DIESEL ONLY. |
| SPECS APPEAR TO SHOW AS BI-FUEL ONLY. |
| |
| 14) NOTE: PLEASE SEE RESPONSE LETTER MENTIONS SHEETS |
| EQ.1, IS THIS NOT E0.1? THIS ONLY APPEARS TO BE A |
| MISPRINT. |
| PLEASE EXPLAIN RATIONAL ON THE SIZING OF THE BREAKERS |
| FROM THE GENERATOR. PLEASE SEE THE EMDP HAS A LOAD OF |
| 238A'S +/- WITH A 300A BREAKER FEEDING THIS 600A PANEL |
| BOARD. WHEREAS THE PANEL "HEQ" WHICH IS ONLY RATED |
| 400A'S AND HAS ONLYA LOAD OF 105A'S +/- , YET HAS A |
| 350A BREAKER AT THE GENERATOR FOR OVER CURRENT |
| PROTECTION. |
| THIS IS UNCLEAR WHY THE EQUIPMENT WITH LOAD WHICH IS |
| SUBSTANTIALLY MORE CONTAINS A LOWER OVER CURRENT |
| PROTECTION. |
| PLEASE EXPLAIN AND CORRELATE. |
| FBC 106.1.2 ADMIN SECT. |
| |
| 15) NOTE: PLEASE SEE FEEDER SCHEDULE ON RISER AND THAT |
| ON MDP2, PLEASE CORRELATE. PLEASE ALSO SEE FEEDER |
| SCHEDULE. |
| |
| 16) NOTE: PLEASE SEE RISER SHOWS A TRANSFORMER T-8 |
| BEING FED FROM HEQ, YET HEQ WITH THE CIRCUITS AS SHOWN |
| ON RISER INDICATE THESE AS ?SPARE? ON SCHEDULE??? |
| PLEASE CORRELATE CIRCUITING AS SHOWN FROM RISER TO |
| PANEL SCHEDULE. |
| FBC 106.1.2 ADMIN SECTION. |
| |
| 17) NOTE: PLEASE HIGH-LIGHT THE SPECIFIC TRANSFER |
| SWITCH BEING USED ON THE MANUFACTURE SPECS/CUT SHEETS |
| SUBMITTED. THERE IS A "SUGGESTED SPECIFICATION" BOOKLET |
| SUBMITTED, HOWEVER PLEASE INDICATE ON SPECS. |
| 110.3,90.7. |
| FBC 106.1.2 |
| |
| |
| |
| |
| ** ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |