Plan Review Notes
Plan Review Notes For Permit 06060723
Permit Number 06060723
Review Stop E
Sequence Number 2
Notes
Date Text
2006-11-20 09:02:28*** UNSAT 2ND REVIEW ***
  
  
 *** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH IS
 STILL IN NEED OF ADDRESSING. PLEASE ALSO WEE NOTES
 WHICH ARE NEW BASED ON REVISED ITEMS NOW SHOWN ON
 PLANS.
  
 ** PLEASE SEE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW AND MARKED WITH AN OK! , NO! (WITH
 FURTHER EXPLANATION) OR SOME MAY BE LABELED WITH OK/NO
 AS PART OF THE COMMENT MAY HAVE BEEN ADDRESSED ONLY.
  
  
 1) NOTE: OK.
  
 2) NOTE: OK.
  
 3) NOTE: OK.
  
 4) NOTE: OK.
  
 5) NOTE:NO, PLEASE SEE THE COMMENT AS PREVIOUSLY
 NOTED WAS TO OBTAIN CORRECT LOCATION TO BE COORDINATED
 WITH THE FIRE MARSHAL'S OFFICE AND SHALL BE SHOWN AND
 NOTED ON THE PLANS THIS WAY. THE PLANS RESPONSE AND
 "KEY NOTE" READS TO BE LOCATED WITH THE OWNER. THIS IS
 THE DECISION OF THE FIRE MARSHAL'S OFFICE AND THE CODE
 ONLY. PLEASE ALSO SEE CODE SECTION AS PREVIOUSLY GIVEN.
 FOR LOCATION REQUIREMENTS
  
 ** PREVIOUS REVIEW NOTE REVIEW # 1 **
 PLEASE SEE GEN ANNUCIATOR PANEL SHALL BE LOCATED IN THE
 FIRE COMMAND ROOM, OR LOCATION OF FACP, NEAREST POINT
 DESIGNATED BY THE FIRE MARSHAL'S OFFICE.
 NFPA-101 CHAPTER 11.8.5.
  
 6) NOTE: OK. RESPONSE LETTER MENTIONS THERE IS A DIESEL
 DRIVEN FIRE PUMP.
  
  
 7) NOTE: OK/ NO,
 PLEASE SEE SPECIFICATIONS FROM THE MANUFACTURE STILL
 INDICATE AS 706 GALLONS. RESPONSE LETTER MENTIONS THAT
 THE TANK WILL BE BAFFLED, YET THE SPECIFICATIONS FROM
 THE MANUFACTURE NEED TO INDICATE THIS AT THIS TIME.
 PLEASE SEE REVIEW COMMENTS FROM OTHER TRADES.
  
  
  
  
 8) NOTE: OK, HOWEVER SEE NEW NOTES.
  
  
 9) NOTE:NO, PLEASE SEE PREVIOUS NOTE, AS SHOWN ON
 PLANS, 4-POLE TRANSFER SWITCHES WILL BE REQUIRED. THIS
 IS BASED ON THE RISER AS SHOWN. THE GENERATOR IS BEING
 SHOWN AS SEPARETLY DERIVED, EVEN THOUGH NOTE MENTIONS
 IT WILL NOT BE.
 PLEASE SEE RISER.
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #1 **
 PLEASE SEE NOTES MENTIONS THAT THE GEN WILL "NOT" BE A
 "SEPARATELY
 DERIVED SYSTEM" YET, GENERATOR SEEMS TO
 BE SHOWN WITH A BOND FROM THE GEN FRAME AND GROUND BAR
 TO THE GEN WINDINGS?
 PLEASE KNOW, IF THIS OCCURS, THEN THIS "IS" A SDS AND
 SHALL THEN CONTAIN A
 4-POLE ATS'S, GE SYSTEM AND NOTED AS SO.
 PLEASE VERIFY AND ADJUST PLANS AS NEEDED.
  
 10) NOTE: NO, PLEASE SEE THIS WAS SUBMITTED; HOWEVER
 PLEASE SEE THE SHEETS IN FACT CONTAIN RAISED SEALS OVER
 A "PHOTO-COPIED" SIGNATURE FROM THE ENGINEER OF RECORD.
 ( MR. ALBERT KWAN) PLEASE SEE FLORIDA STATUTES 471.025,
 AND FLORIDA ADMINISTRATIVE CODE 61G15-23.002. PLEASE
 KNOW THIS IS REVIEW WHETHER OR NOT COMMENT IS MADE BY
 BUILDING REVIEW.
 PLEASE ALSO SEE SHEET MENTIONS TO BE 6INCHES ABOVE
 FLOOR ELEVATION HOWEVER, EQUIPMENT SHALL BE 6 INCHES
 ABOVE THE BFE BASED ON THE 100 YR YEAR STORM SURGES
 LEVELS OR SURGE LEVELS BASED ON A CAT 4 STORM. PLEASE
 SEE SLOSH CHARTS ETC.
 PLEASE SEE SECTIONS GIVEN IN PREVIOUS REVIEW NOTE.
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #1 **
 PLEASE BUILDING REVIEW COMMENTS WITH RESPECT TO THE
 GEN SLAB DETAIL. PLEASE SEE NO DETAIL, CONNECTIONS,
 ELEVATIONS WERE SUBMITTED.
 PLEASE ALSO SEE NOTE MENTIONS THE GEN @ OR ABOVE BFE.
 PLEASE KNOW, THE GEN/ ASSOCIATED EQUIPMENT SHALL BE 6"
 ABOVE THE BFE.
 PLEASE SEE NFPA-110 CHAPTER 7, 7.2, 7.3,
 7.4, 7.9 ETC.
 ** PLEASE KNOW, DUE TO THE SIZE, WEIGHT, EPSS
 REQUIREMENTS ETC,THE SLAB WILL BE REQUIRED TO BE
 SIGNED, DATED AND SEALED BY AN ENGINEER.
 FS 471.003
  
 11) NOTE:NO, SAME NOTE.
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #1 **
 PLEASE BE SURE THE ENGINEER OF RECORD SIGNS PLANS WITH
 HIS LEGAL/EASILY RECOGNIZABLE SIGNATURE KNOWN TO THIS
 OFFICE AND ON RECORD IN THIS OFFICE.
 FS 471.025, FAC 61G15-23.002
  
  
 **** NEW NOTES FROM THE 2ND REVIEW ***
  
 12) NOTE: PLEASE SUBMIT THE MANUFACTURE
 SPECIFICATION/CUT SHEETS ON THE WP HOUSING FOR THE
 GENERATOR.
 FBC 106.1.2,
 110.3,90.7
  
 13) NOTE: PLEASE BE SURE EITHER PLANS OR MANUFACTURE
 SPECIFICATIONS INDICATE THE FUEL CONSUMPTION BASED ON
 DIESEL ONLY.
 SPECS APPEAR TO SHOW AS BI-FUEL ONLY.
  
 14) NOTE: PLEASE SEE RESPONSE LETTER MENTIONS SHEETS
 EQ.1, IS THIS NOT E0.1? THIS ONLY APPEARS TO BE A
 MISPRINT.
 PLEASE EXPLAIN RATIONAL ON THE SIZING OF THE BREAKERS
 FROM THE GENERATOR. PLEASE SEE THE EMDP HAS A LOAD OF
 238A'S +/- WITH A 300A BREAKER FEEDING THIS 600A PANEL
 BOARD. WHEREAS THE PANEL "HEQ" WHICH IS ONLY RATED
 400A'S AND HAS ONLYA LOAD OF 105A'S +/- , YET HAS A
 350A BREAKER AT THE GENERATOR FOR OVER CURRENT
 PROTECTION.
 THIS IS UNCLEAR WHY THE EQUIPMENT WITH LOAD WHICH IS
 SUBSTANTIALLY MORE CONTAINS A LOWER OVER CURRENT
 PROTECTION.
 PLEASE EXPLAIN AND CORRELATE.
 FBC 106.1.2 ADMIN SECT.
  
 15) NOTE: PLEASE SEE FEEDER SCHEDULE ON RISER AND THAT
 ON MDP2, PLEASE CORRELATE. PLEASE ALSO SEE FEEDER
 SCHEDULE.
  
 16) NOTE: PLEASE SEE RISER SHOWS A TRANSFORMER T-8
 BEING FED FROM HEQ, YET HEQ WITH THE CIRCUITS AS SHOWN
 ON RISER INDICATE THESE AS ?SPARE? ON SCHEDULE???
 PLEASE CORRELATE CIRCUITING AS SHOWN FROM RISER TO
 PANEL SCHEDULE.
 FBC 106.1.2 ADMIN SECTION.
  
 17) NOTE: PLEASE HIGH-LIGHT THE SPECIFIC TRANSFER
 SWITCH BEING USED ON THE MANUFACTURE SPECS/CUT SHEETS
 SUBMITTED. THERE IS A "SUGGESTED SPECIFICATION" BOOKLET
 SUBMITTED, HOWEVER PLEASE INDICATE ON SPECS.
 110.3,90.7.
 FBC 106.1.2
  
  
  
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
 **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF
 THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE
 DO NOT HESITATEIN CONTACTING THIS REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717