Plan Review Notes For Permit 06060723 |
Permit Number |
06060723 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-08-21 00:00:00 | DENIED: | | 1.PLEASE PROVIDE DISTANCES/CLEARANCES | | TO THE FOLLOWING; PROPERTY LINES, | | BUILDINGS, FRESH AIR INTAKES, WINDOWS, | | DOORS, LOUVERS, ETC.SHOW COMPLIANCE | | WITH 2004 FMC 401.5. | | | | 2.INDICATE IF PROTECTION FROM DAMAGE | | IS REQUIRED IN ACCORDANCE WITH 2004 FMC | | 303.4. | | | | 3.PROVIDE DETAIL INFORMATION ON THE | | ANCHORING OF THE GENERATOR. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719 OR | | E-MAIL [email protected]. |
|