Plan Review Notes For Permit 06060723 |
Permit Number |
06060723 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-08-18 00:00:00 | ***DENIED*** | | | | 1) PLEASE SEE OTHER REVIEW COMMENTS | | REGARDING ADDRESSING AND MAKE | | CORRECTION. THE ADDRESS SHOULD REFLECT | | 1001 OKEECHOBEE BLVD. | | | | 2) NFPA 101, 2003 EDITION SHALL BE | | REFERENCED. | | | | 3) PLEASE CLEARLY IDENTIFY LOCATION OF | | GENERATOR AND FUEL TANK WITH RELATION TO | | BUILDING OPENINGS AND ILLUSTRATE | | DISTANCES. PLEASE SUBMIT SITE PLAN FOR | | REVIEW. | | | | 4) WORK TO COMPLY WITH NFPA 110, 2002 | | EDITION. | | | | 5) DEPENDANT UPON LOCATION OF EQUIPMENT, | | SAFEGUARDS AGAINST MECHANICAL DAMAGE MAY | | BE REQUIRED AND SHALL BE ILLUSTRATED. | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | FIRE PLAN REVIEW (561) 805-6722 |
|