Date |
Text |
2006-06-30 00:00:00 | ********* UNSAT ********* |
| |
| 1) NOTE: PLEASE SEE ADDRESSING REVIEW |
| AND COMMENTS AS THE CORRECT ADDRESS FOR |
| THE MARRIOT IS 1001 OKEECHOBEE BLVD. |
| THIS ADDRESS WAS CHANGED A COUPLE OF |
| YEARS AGO. |
| PLEASE ADJUST ALL PLANS/TITLE BLOCKS ARE |
| REQUIRED FAC 61G15-23.002/61G1-16.004 |
| |
| 2) NOTE: PLEASE CLARIFY THE KW RATING OF |
| THE GEN AS ONE SHEET IN THE |
| SUBMITTAL/SPEC PACKAGE CONTAINS 400KW? |
| |
| 3) NOTE: PLEASE BE SURE TO PROVIDE ALL MANUFACTURES |
| CUT/SPEC SHEETS FOR GEN AND |
| ATS. APPEARS TO BE MISSING COVER SHEETS |
| ETC. |
| FBC ADMIN SECT 106.1.2 |
| |
| 4) NOTE: PLEASE SEE THAT PLANS REFLECT |
| ALL CURRENT CODES IN AFFECT. |
| NFPA-70 2002, NFPA-101 2003, NFPA-110 |
| 2002. |
| |
| 5) NOTE: PLEASE SEE GEN ANNUCIATOR PANEL |
| SHALL BE LOCATED IN THE FIRE COMMAND |
| ROOM, OR LOCATION OF FACP, NEAREST POINT DESIGNATED BY |
| THE FIRE MARSHAL'S OFFICE. |
| NFPA-101 CHAPTER 11.8.5. |
| |
| 6) NOTE: PLEASE CLARIFY IF THE FIRE PUMP |
| IS FED FROM THIS GEN. ?? |
| IF SO, PLEASE KNOW, THERE MUST BE A MIN |
| OF 8HRS "ON-SITE" FUEL FOR 100% OF THE |
| FULL LOAD RATING OF THE FIRE PUMP AND |
| OTHER ASSOCIATED EM EQUIPMENT.2003 |
| NFPA-20 9.6.2.2 |
| PLEASE ALSO PROVIDE GPH WITHOUT THE TIE |
| IN OF THE NAT GAS LINE AND WITH THE TIE |
| IN OF THE NAT GAS LIN. |
| |
| |
| 7) NOTE: PLEASE SEE FIRE REVIEW AND |
| MECHANICAL REVIEW COMMENTS WITH RESPECT |
| TO FUEL PIPING/ TANK SIZE AND STORAGE. |
| 7.9.12LISTED GENERATOR SUB-BASE |
| SECONDARY CONTAINMENT FUEL TANKS OF 2498 |
| L (660 GAL) CAPACITY AND BELOW SHALL BE |
| PERMITTED TO BE INSTALLED OUTDOORS OR |
| INDOORS WITHOUT DIKING OR REMOTE |
| IMPOUNDING. |
| 7.9.12.1A MINIMUM CLEARANCE OF 0.9 M |
| (36 IN.) SHALL BE MAINTAINED ON ALL |
| SIDES. |
| 7.9.3.1GALVANIZED FUEL LINES SHALL NOT |
| BE USED. |
| ** |
| PLEASE SEE TANK SIZE IS BEING INDICATED |
| AS 706 GALS. |
| |
| |
| 8) NOTE: PLEASE SEE ATS-LS IS BEING FROM |
| A 400A OCP AND EQUIPMENT IS RATED FOR |
| 300A'S AND FEED FROM GEN IS 250A'S?? |
| PLEASE CORRELATE. |
| 215.5 |
| |
| 9) NOTE: PLEASE SEE NOTES MENTIONS THAT |
| THE GEN WILL "NOT" BE A "SEPARATELY |
| DERIVED SYSTEM" YET, GENERATOTR SEEMS TO |
| BE SHOWN WITH A BOND FRON THE GEN FRAME |
| AND GRND BAR TO THE GEN WINDINGS? |
| PLEASE KNOW, IF THIS OCCURS, THEN THIS |
| "IS" A SDS AND SHALL THEN CONTAIN A |
| 4-POLE ATS'S, GE SYSTEM ANDNOTED AS |
| SO. |
| PLEASE VERIFY AND ADJUST PLANS AS |
| NEEDED. |
| |
| 10) NOTE: PLEASE BUILDING REVIEW |
| COMMENTS WITH RESPECT TO THE GEN SLAB |
| DETAIL. PLEASE SEE NO DETAIL, |
| CONNECTIONS, ELEVATIONS WERE SUBMITTED. |
| PLEASE ALSO SEE NOTE MENTIONS THE GEN @ |
| OR ABOVE BFE. PLEASE KNOW, THE GEN/ |
| ASSOCIATED EQUIPMENT SHALL BE 6" ABOVE |
| THE BFE. |
| PLEASE SEE NFPA-110 CHAPTER 7, 7.2,7.3, |
| 7.4,7.9 ETC. |
| ** PLEASE KNOW, DUE TO THE SIZE, WEIGHT, |
| EPSS REQUIREMNTS ETC,THE SLAB WILL BE |
| REQUIRED TO BE SIGNED, DATED AND SEALED |
| BY AN ENGINEER. |
| FS 471.003 |
| |
| 11) NOTE: PLEASE BE SURE THE ENGINEER OF |
| RECORD SIGNS PLANS WITH HIS LEGAL/EASILY RECOGNIZABLE |
| SIGNATURE KNOWN TO THIS |
| OFFICE AND ON RECORD IN THIS OFFICE. |
| FS 471.025, FAC 61G15-23.002 |
| |
| ** PLEASE BE SURE TO SEE ANY OTHER |
| COMMENTS FROM OTHER TRADES WHICH MAY |
| AFFECT ELECTRICAL PLANS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |