Plan Review Notes For Permit 06060723
Permit Number 06060723
Review Stop E
Sequence Number 1
Notes
Date Text
2006-06-30 00:00:00********* UNSAT *********
  
 1) NOTE: PLEASE SEE ADDRESSING REVIEW
 AND COMMENTS AS THE CORRECT ADDRESS FOR
 THE MARRIOT IS 1001 OKEECHOBEE BLVD.
 THIS ADDRESS WAS CHANGED A COUPLE OF
 YEARS AGO.
 PLEASE ADJUST ALL PLANS/TITLE BLOCKS ARE
 REQUIRED FAC 61G15-23.002/61G1-16.004
  
 2) NOTE: PLEASE CLARIFY THE KW RATING OF
 THE GEN AS ONE SHEET IN THE
 SUBMITTAL/SPEC PACKAGE CONTAINS 400KW?
  
 3) NOTE: PLEASE BE SURE TO PROVIDE ALL MANUFACTURES
 CUT/SPEC SHEETS FOR GEN AND
 ATS. APPEARS TO BE MISSING COVER SHEETS
 ETC.
 FBC ADMIN SECT 106.1.2
  
 4) NOTE: PLEASE SEE THAT PLANS REFLECT
 ALL CURRENT CODES IN AFFECT.
 NFPA-70 2002, NFPA-101 2003, NFPA-110
 2002.
  
 5) NOTE: PLEASE SEE GEN ANNUCIATOR PANEL
 SHALL BE LOCATED IN THE FIRE COMMAND
 ROOM, OR LOCATION OF FACP, NEAREST POINT DESIGNATED BY
 THE FIRE MARSHAL'S OFFICE.
 NFPA-101 CHAPTER 11.8.5.
  
 6) NOTE: PLEASE CLARIFY IF THE FIRE PUMP
 IS FED FROM THIS GEN. ??
 IF SO, PLEASE KNOW, THERE MUST BE A MIN
 OF 8HRS "ON-SITE" FUEL FOR 100% OF THE
 FULL LOAD RATING OF THE FIRE PUMP AND
 OTHER ASSOCIATED EM EQUIPMENT.2003
 NFPA-20 9.6.2.2
 PLEASE ALSO PROVIDE GPH WITHOUT THE TIE
 IN OF THE NAT GAS LINE AND WITH THE TIE
 IN OF THE NAT GAS LIN.
  
  
 7) NOTE: PLEASE SEE FIRE REVIEW AND
 MECHANICAL REVIEW COMMENTS WITH RESPECT
 TO FUEL PIPING/ TANK SIZE AND STORAGE.
 7.9.12LISTED GENERATOR SUB-BASE
 SECONDARY CONTAINMENT FUEL TANKS OF 2498
 L (660 GAL) CAPACITY AND BELOW SHALL BE
 PERMITTED TO BE INSTALLED OUTDOORS OR
 INDOORS WITHOUT DIKING OR REMOTE
 IMPOUNDING.
 7.9.12.1A MINIMUM CLEARANCE OF 0.9 M
 (36 IN.) SHALL BE MAINTAINED ON ALL
 SIDES.
 7.9.3.1GALVANIZED FUEL LINES SHALL NOT
 BE USED.
 **
 PLEASE SEE TANK SIZE IS BEING INDICATED
 AS 706 GALS.
  
  
 8) NOTE: PLEASE SEE ATS-LS IS BEING FROM
 A 400A OCP AND EQUIPMENT IS RATED FOR
 300A'S AND FEED FROM GEN IS 250A'S??
 PLEASE CORRELATE.
 215.5
  
 9) NOTE: PLEASE SEE NOTES MENTIONS THAT
 THE GEN WILL "NOT" BE A "SEPARATELY
 DERIVED SYSTEM" YET, GENERATOTR SEEMS TO
 BE SHOWN WITH A BOND FRON THE GEN FRAME
 AND GRND BAR TO THE GEN WINDINGS?
 PLEASE KNOW, IF THIS OCCURS, THEN THIS
 "IS" A SDS AND SHALL THEN CONTAIN A
 4-POLE ATS'S, GE SYSTEM ANDNOTED AS
 SO.
 PLEASE VERIFY AND ADJUST PLANS AS
 NEEDED.
  
 10) NOTE: PLEASE BUILDING REVIEW
 COMMENTS WITH RESPECT TO THE GEN SLAB
 DETAIL. PLEASE SEE NO DETAIL,
 CONNECTIONS, ELEVATIONS WERE SUBMITTED.
 PLEASE ALSO SEE NOTE MENTIONS THE GEN @
 OR ABOVE BFE. PLEASE KNOW, THE GEN/
 ASSOCIATED EQUIPMENT SHALL BE 6" ABOVE
 THE BFE.
 PLEASE SEE NFPA-110 CHAPTER 7, 7.2,7.3,
 7.4,7.9 ETC.
 ** PLEASE KNOW, DUE TO THE SIZE, WEIGHT,
 EPSS REQUIREMNTS ETC,THE SLAB WILL BE
 REQUIRED TO BE SIGNED, DATED AND SEALED
 BY AN ENGINEER.
 FS 471.003
  
 11) NOTE: PLEASE BE SURE THE ENGINEER OF
 RECORD SIGNS PLANS WITH HIS LEGAL/EASILY RECOGNIZABLE
 SIGNATURE KNOWN TO THIS
 OFFICE AND ON RECORD IN THIS OFFICE.
 FS 471.025, FAC 61G15-23.002
  
 ** PLEASE BE SURE TO SEE ANY OTHER
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]