Plan Review Notes For Permit 06060696 |
Permit Number |
06060696 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-06-26 00:00:00 | **** UNSAT **** | | | | 1) NOTE: PLEASE BE SURE SITE/SURVEY | | INDICATES THE MIN BASE FLOOD ELEVATION | | (BFE) AND PLEASE INDICATE SLAB AT A MIN | | OF 6" ABOVE BFE. | | | | *** PLEASE ALSO KNOW THAT A FLOOD | | ELEVATION CERTIFICATE WILL ALSO BE | | REQUIRED BEFORE FINAL ELECTRICAL | | INSPECTON. | | | | 2) NOTE: PLEASE SEE THAT MANUFACTURES | | SPEC/CUT SHEETS INDICATE ALL MIN | | CLEARENCES AROUND EQUIPMENT. | | 110.3, 215.5 | | FBC ADMIN SECT 106.1.2 | | | | 3) NOTE: PLEASE BE SURE ALL | | PLANS/DESIGNS ALSO CONTAIN THE PRINTED | | NAME AND SIGNATURE OF THE PERSON | | RESPONSIBLE FOR PLANS. | | FBC 106.1.2 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|