Plan Review Notes For Permit 06060693 |
Permit Number |
06060693 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-06-22 00:00:00 | DENIED | | | | 1) FBC 1019.1.5 STATES THAT AN EXIT | | ENCLOSURE SHALL NOT BE USED FOR ANY | | PURPOSE OTHER THAN MEANS OF EGRESS. | | FBC 1019.1.5 ENCLOSURES UNDER STAIRWAYS. | | THE WALLS AND SOFFITS WITHIN ENCLOSED | | USABLE SPACES UNDER ENCLOSED AND | | UNENCLOSED STAIRWAYS SHALL BE PROTECTED | | BY 1-HOUR FIRE-RESISTANCE-RATED | | CONSTRUCTION, OR THE FIRE-RESISTANCE | | RATING OF THE STAIRWAY ENCLOSURE, | | WHICHEVER IS GREATER. ACCESS TO THE | | ENCLOSED USABLE SPACE SHALL NOT BE | | DIRECTLY FROM WITHIN THE STAIR | | ENCLOSURE. | | | | 2) THE OWNER OF RECORD ON THE | | APPLICATION DOES NOT CORRESPOND WITH | | CITY RECORDS. PLEASE SUBMIT PROOF OF | | OWNERSHIP, SO THAT RECORDS CAN BE | | UPDATED. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 |
|