Plan Review Notes
Plan Review Notes For Permit 06060613
Permit Number 06060613
Review Stop E
Sequence Number 1
Notes
Date Text
2006-06-18 00:00:00******UNSAT ******
  
 1) NOTE: PLEASE SEE OWNERSHIP
 INFORMATION NEEDS TO BE UPDATED, SEE
 NOTES FROM ADDRESSING ETC.
  
 2) NOTE: PLEASE SUBMIT ELECTRICAL
 PLAN/DRAWING FOR PROPOSED SCOPE OF WORK
 TO BE PERFORMED.
 PLEASE SEE TWO SEPARATE SHEETS
 SUBMITTED, EACH SHEET IS NOT CLEAR.
 PLEASE SEE THAT TWO SETS OF ALL SHEETS
 ARE REQUIRED.
 PLEASE SUBMIT CLEAR AND CONCISE PLANS
 WITH AMIN OF DRAFTMAN'S QUALITY.
 PLEASE SEE SHEETS WHICH ARE HAND DRAWN
 IN PEN ARE NOT PERMITED.
 PLEASE SEE FBC 2004 106.3.1, 106.2.1
 ADMIN SEC AS ADOPTED BY CITY OF WEST
 PALM BEACH.
  
 3) NOTE: PLEASE SEE MIN REQUIREMENT S
 FOR SD'S INSIDE AND OUTSIDE ALL SLEEPING
 RMS.
 NFPA-72 11.5.1.1
  
 4) NOTE: PLEASE SEE MIN CIRCUITING FOR
 ARC FAULT PROTECTION OF ANY NEW
 ELECTRICAL IN NEW BEDRM.210.12, 2002
 NEC.
  
 ** AS OTHER ELECTRICAL SHEETS SEEM TO
 INDICATE ALL NEW ELECTRICAL WIRING,
 PLEASE SUBMIT COMPLETE PLANS, PANEL
 SCHEDULES WITH ALL MIN CIRCUITS,
 CONDUCTOR SIZES, OCP ETC.
 215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
 *** PLEASE KNOW NOC, SHOWS NEW OWNER,
 YET SYSTEM SHOWS SOMEONE ELSE.