2006-06-18 00:00:00 | ******UNSAT ****** |
| |
| 1) NOTE: PLEASE SEE OWNERSHIP |
| INFORMATION NEEDS TO BE UPDATED, SEE |
| NOTES FROM ADDRESSING ETC. |
| |
| 2) NOTE: PLEASE SUBMIT ELECTRICAL |
| PLAN/DRAWING FOR PROPOSED SCOPE OF WORK |
| TO BE PERFORMED. |
| PLEASE SEE TWO SEPARATE SHEETS |
| SUBMITTED, EACH SHEET IS NOT CLEAR. |
| PLEASE SEE THAT TWO SETS OF ALL SHEETS |
| ARE REQUIRED. |
| PLEASE SUBMIT CLEAR AND CONCISE PLANS |
| WITH AMIN OF DRAFTMAN'S QUALITY. |
| PLEASE SEE SHEETS WHICH ARE HAND DRAWN |
| IN PEN ARE NOT PERMITED. |
| PLEASE SEE FBC 2004 106.3.1, 106.2.1 |
| ADMIN SEC AS ADOPTED BY CITY OF WEST |
| PALM BEACH. |
| |
| 3) NOTE: PLEASE SEE MIN REQUIREMENT S |
| FOR SD'S INSIDE AND OUTSIDE ALL SLEEPING |
| RMS. |
| NFPA-72 11.5.1.1 |
| |
| 4) NOTE: PLEASE SEE MIN CIRCUITING FOR |
| ARC FAULT PROTECTION OF ANY NEW |
| ELECTRICAL IN NEW BEDRM.210.12, 2002 |
| NEC. |
| |
| ** AS OTHER ELECTRICAL SHEETS SEEM TO |
| INDICATE ALL NEW ELECTRICAL WIRING, |
| PLEASE SUBMIT COMPLETE PLANS, PANEL |
| SCHEDULES WITH ALL MIN CIRCUITS, |
| CONDUCTOR SIZES, OCP ETC. |
| 215.5 |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |
| |
| |
| |
| |
| *** PLEASE KNOW NOC, SHOWS NEW OWNER, |
| YET SYSTEM SHOWS SOMEONE ELSE. |