Plan Review Notes
Plan Review Notes For Permit 06060604
Permit Number 06060604
Review Stop M
Sequence Number 1
Notes
Date Text
2006-07-14 00:00:00* IT HAS BEEN BROUGHT TO OUR ATTENTION
 THAT THE JOB AT 7701 MARTIN AVE. DID NOT
 HAVE CENTRAL AIR CONDITIONING, BUT HAD
 WINDOW A/C UNITS, THEREFORE THE
 DESCRIPTION OF WORK TO BE DONE AS "EXACT
 CHANGE OUT " WAS NOT CORRECT.
 PLEASE BE ADVISED THAT FALSIFIED
 DOCUMENTS MAY BE SENT TO THE STATE OF
 FLORIDA DBPR .
  
 *** PERMIT DENIED ***
 1) PLEASE SUBMITMANUAL J CALCULATIONS,
 PER 2004 FBC 13-607.1.ABC.1 .
  
 2) SHOW LOCATION OF CONDENSER UNIT, AND
 DRAIN LINE ON MECHANICAL PLANS.
  
 3) LABEL ALL ROOMS (KITCHEN, BEDROOM,
 BATHROOM, ECT.)
  
 4) NEED JOB ADDRESS ON PLANS.
  
 5) ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE DESIGN. PER FBC 104.2.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.