Plan Review Notes For Permit 06060583 |
Permit Number |
06060583 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-06-23 00:00:00 | ***** UNSAT *********** | | | | 1) NOTE: PLEASE PROVIDE LOCATION ALL ALL | | EQUIPMENT ON HOUSE LAYOUT PLANS. | | WHERE IS THE ELECTRICLA PANEL LOCATED? | | MUST MEET 225.34 | | | | 2) NOTE: PLEASE SEE ZONING COMMNETS AND | | ALL DIMENSIONS TO BE SHOWN. | | ** PLEASE BE SURE MANUFACTURES CUT/SPECS | | SHEETS CLEARLY INDICATE MIN CLEARENCES | | ON ALL SIDES OF EQUIPMENT. | | **PLEASE SEE MECH COMMENTS. | | | | 3) NOTE: PLEASE SEE GROUNDING ELECTRODE | | CONDUCTOR IS TO BE SIZED PER 250.66 | | THE SIZE OF #6 SHOWN AS EXISTING DOES | | NOT MEET NEC AND WOULD BE REQ'D TO BE | | UPGRADED. | | | | 4) NOTE: PLEASE SEE BLDG COMMENTS AS NO | | SLAB DETAIL WAS SUBMITTED. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] | | |
|