Date |
Text |
2006-10-05 00:00:00 | |
| |
| |
| DENIED |
| |
| PREVIOUS REVIEW NOTES NOT ADDRESSED: |
| |
| 1) OK |
| |
| 2) OK VALUE ADJUSTED AND INCREASED |
| PERMIT FEES ARE DUE ($255.16) |
| |
| 3) OK FEES ADDED TO PERMIT FEES |
| |
| 4) OK |
| |
| 5) OK |
| |
| 6) THE PERMIT APPLICATION SHALL INCLUDE |
| TWO COPIES OF EACH PRODUCT APPROVAL THAT |
| IS RELEVANT PER 9B-72. THESE SHOULD |
| INCLUDE THE FLORIDA STATE APPROVAL COVER |
| PAGES, AND THE PRODUCT NOA THAT LISTS |
| THE SYSTEM COMPONENTS/ FASTENER LIST |
| PAGES, THE PAGES WITH THE CHOSEN |
| ASSEMBLY/ SYSTEM TO BE USED AND THE |
| GENERAL LIMITATIONS PAGE. ALL CAN BE |
| FOUND ON WWW.FLORIDABUILDING.ORG |
| |
| ******NO STATE OF FLORIDA COVER PAGES |
| WERE SUBMITTED PLEASE SEE ABOVE WEB SITE |
| FOR THE STATE OF FLORIDA PRODUCT |
| APPROVAL COVER SHEETS******* |
| PLEASE KNOW THE CITY OF WEST PALM BEACH |
| REQUIRES THE FLORIDA STATE PRODUCT |
| APPROVAL COVER SHEETS WHEN AVAILABLE. |
| THEY CAN BE SEARCHED FOR ON |
| WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE |
| AND NOT SUBMITTED APPLICATIONS WILL BE |
| DENIED |
| |
| 7) THE FOLLOWING INFORMATION IS NEEDED |
| OR MISSING FROM THE PRODUCT APPROVALS |
| |
| A) WHERE APPLICABLE THE BUILDING |
| OFFICIAL REQUIRES THE STATE OF FLORIDA |
| PRODUCT APPROVALS COMPLETE WITH STATE |
| COVER SHEET AND APPLICABLE NOA |
| |
| ********SEE ABOVE NOTE******** |
| |
| B) OK |
| |
| C) CHOOSE ASSEMBLY THAT WILL BE USED IN |
| ROOFING NOA (PG.5 OR 6) ALSO SEE THAT |
| THEY WILL NOT MEET THE PRESSURES |
| REQUIRED FOR ZONES 2 & 3 OF ROOF WITHOUT |
| ENHANCED FASTENING. LIMITATION #7 ALLOWS |
| FOR THIS BUT THE CALCULATIONS SHALL BE |
| PREPARED SIGNED AND SEALED BY A DESIDGN |
| PROFFESIONAL. (SEE PG. 7 LIMITATION#7) |
| |
| ******PROVIDE ENGINEERS CALCULATIONS FOR |
| THE ENHANCED FASTENING IN THE CORNER, |
| ZONE 3******* |
| |
| D) WINDOWS ARE IMPACT RESISTANT BUT |
| DOORS ARE NOT AND WILL REQUIRE IMPACT |
| PROTECTION, IF USING THESE DOORS PROVIDE |
| PRODUCT APPROVAL FOR SHUTTERS |
| |
| ******THE JELD WEN PRODUCT APPROVAL IS |
| FOR A GLAZED NON IMPACT DOOR, PLEASE |
| PROVIDE AN APPROVED IMPACT RESISTANT |
| PRODUCT APPROVALFOR THE DOOR |
| |
| E) PROVIDE PRODUCT APPROVALS FOR PRECAST |
| CONCRETE LINTELS |
| |
| ******NOT SUBMITTED****** |
| |
| 7) OK |
| |
| 8) PROVIDE A LINTEL SCHEDULE, TYPICAL |
| DETAIL PAGE 2 WILL NOT WORK AS TOP OF |
| BEAM AT 8'-0" AND DOOR AND WINDOWS AT |
| 6'-8" TO TOP. TOTAL 16" LESS 8" BOND |
| BEAM LEAVES 8" AND DETAIL SHOWS |
| 16"LINTEL |
| |
| *******NOT CHANGED ON THE DRAWING******* |
| |
| 9) OK, REMOVED FROM DRAWING |
| |
| 10) PROVIDE CORRECT ROOF COVERING ON |
| DRAWINGS AND SPECIFY THE NAILING PATTERN |
| PER FASTENING TABLE 2304.9.1 FBC |
| |
| ******NOT ADDRESSED ON THE DRAWING***** |
| |
| 11) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT IS REQUIRED PRIOR TO |
| A PERMIT BEING ISSUED |
| |
| ******PER 713.13(2) F.S. |
| IF THE IMPROVEMENT DESCRIBED IN THE NOC |
| HAS NOT COMMENCED WITHIN 90 DAYS OF |
| RECORDING THE NOTICE IS VOID PLEASE |
| RERECORD NOC ******** |
| |
| |
| NEW NOTES: |
| |
| 1) PER 106.1.3 FBC* THE BUILDING |
| OFFICIAL MAY ESTABLISH THROUGH |
| DEPARTMENTAL POLICY, STANDARDS FOR PLANS |
| AND SPECIFICATIONS "NO WHITE OUT, PENCIL |
| OR INK" |
| |
| |
| NOTE: FBC = FLORIDA BUILDING CODE 2004 |
| FBC* = WEST PALM BEACH |
| ADMINISTATIVE AMMENDMENTS TO FBC |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| BLDG PLAN REVIEW |
| ADRIAN MORSE |
| 561-805-6716 |
| |
| |
| |
| |
| |
| |