Plan Review Notes
Plan Review Notes For Permit 06060549
Permit Number 06060549
Review Stop M
Sequence Number 1
Notes
Date Text
2006-10-06 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS CAN NOT BE ON
 FORM 600C-04 AS THE ADDITION IS OVER 600
 SQUARE FEET, PER 2004 FBC 13-600.3.C .
 PLEASE SUBMIT NEW ENERGY CALCULATIONS
 USING FORM 'A' OR 'B'.
  
 2) NO MECHANICAL PLANS WERE SUBMITTED
 FOR REVIEW. PLEASE SUBMIT MECHANICAL
 PLANS FOR REVIEW, REQUIRED PER 2004 FBC
 WPB AMEND. 106.3.5.4 (10).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.