Plan Review Notes For Permit 06060549 |
Permit Number |
06060549 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-06-20 00:00:00 | | | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} THE ENGINEER OF RECORD SHALL INDICATE | | THE CERTIFICATE OF AUTHORIZATIONNUMBER | | REQUIRED BY 61G15-23.002FLORIDA | | ADMINISTRATIVE CODE. | | | | 2} KITCHEN RECEPTACLE SPACING MUST | | COMPLY WITH 210.52(A), 210.52(C), AND | | 210.8(A)(6) GFI. THIS IS AN ELECTRICAL | | ISSUE SEPARATE FROM ZONING. IF THE | | KITCHEN IS ON THE PLAN IT MUST COMPLY | | WITH THE NEC. | | | | 3} PROVIDE A LOAD CALCULATION PER | | 220.31, INCLUDE ADDED LOADS. INDICATE | | THE RATING OF THE EXISTING SERVICE. | | | | 4} SUBMIT A PANEL SCHEDULE PER 408.4 NEC | | AND 106.3.5.4(8) FBC. | | | | 5} RECEPTACLE SPACING MUST COMPLY WITH | | 210.52(A)(1) AND 210.52(A)(2). | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | WILLIAM R. TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561) 805-6718 | | |
|