Date Text
2006-06-20 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE ENGINEER OF RECORD SHALL INDICATE
 THE CERTIFICATE OF AUTHORIZATIONNUMBER
 REQUIRED BY 61G15-23.002FLORIDA
 ADMINISTRATIVE CODE.
  
 2} KITCHEN RECEPTACLE SPACING MUST
 COMPLY WITH 210.52(A), 210.52(C), AND
 210.8(A)(6) GFI. THIS IS AN ELECTRICAL
 ISSUE SEPARATE FROM ZONING. IF THE
 KITCHEN IS ON THE PLAN IT MUST COMPLY
 WITH THE NEC.
  
 3} PROVIDE A LOAD CALCULATION PER
 220.31, INCLUDE ADDED LOADS. INDICATE
 THE RATING OF THE EXISTING SERVICE.
  
 4} SUBMIT A PANEL SCHEDULE PER 408.4 NEC
 AND 106.3.5.4(8) FBC.
  
 5} RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A)(1) AND 210.52(A)(2).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561) 805-6718
  