2006-06-13 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE SPECOFY NEW CIRCUIT IN
 WHICH THE SD'S ARE DONE.
 PLEASE SEE NFPA-72 11.5.1.1, AND 210.12B
 FOR REQUIRED ARC FAULT PROTECTION.
  
 2) NOTE: PLEASE SEE WASHER CIRCUIT IS
 BEING SHOWN AS OPTIONAL?? PLEASE KNOW AS
 THIS IS NOW BEING CONSIDERED AND
 CONVERTED TO A CONDO/RESIDENCE, A
 LAUNDRY CIRCUIT WILL BE REQUIRED AT
 1500VA
 210.11,210.52F 220.16
  
 3) NOTE:PLEASE KNOW, ANY ITEMS
 INDICATED AS "OPT" ON PLANS, WILL BE
 REQUIRED TO BE REVISED BEFORE ROUGH.
  
 4) NOTE: PLEASE SEE 44 SETS OF PLAN
 LAYOUTS WILL BE REQUIRED FOR EACH
 PERMIT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  